| Plan Review Notes For Permit 15031359 |
| Permit Number |
15031359 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-09 07:35:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PERMIT DESCRIPTION IS NOT CONSISTENT WITH PLAN. | | | PLANS SHOULD SHOW SCOPE, NATURE, AND LOCATION OF | | | PROPOSED WORK, FBC 107. | | | | | | 2. PLAN SHOWS A NEW WOOD DECK. PROVIDE PLANS. PLANS | | | SHOULD BE ARCHITECTURAL QUALITY, TO SCALE. IMPROVEMENTS | | | SUBJECT TO LOADS (WIND, LIVE, ETC.) ARE TO BE DESIGNED | | | USING A METHOD IN FBC 2010 RESIDENTIAL 301; | | | CALCULATIONS MAY BE REQUIRED IF PLANS ARE NOT PREPARED | | | BY A DESIGN PROFESSIONAL, FBC 107. | | | | | | 3. PLANS ARE TO INCLUDE THE PRINTED NAME AND SIGNATURE | | | OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN, | | | FBC 107. | | | | | | 4. A STOP WORK ORDER HAS BEEN ISSUED AT THIS LOCATION. | | | PLANS ARE TO INCLUDE ALL WORK DONE WITHOUT PERMIT. ON | | | THE PLAN, IT WILL BE CONSIDERED "PROPOSED" OR "WORK | | | DONE WITHOUT PERMIT," NOT "EXISTING." ANYTHING | | | INDICATED AS "EXISTING" ON THE PLAN ARE TO BE | | | IMPROVEMENTS WHICH HAVE BEEN PERMITTED, INSPECTED, AND | | | FINALED. | | | | | | | | | | | | |
|