| 2015-05-27 12:50:28 | 5/27/2015 |
| | PROJECT: SNED ADDITION |
| | PERMIT#: 15031318 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) SMOKE DETECTORS TO BE INSTALLED IN ACCORDANCE WITH |
| | THE FBC-R 314, AND 315 THROUGHOUT THE DWELLING UNIT, |
| | NOT JUST THE RENOVATION. THE LOCATIONS INDICATED ON THE |
| | PLAN FOR THE INSTALLATION OF SMOKE DETECTORS ARE NOT |
| | REQUIRED ACCORDING TO THE FBC-R 314, 315. PLEASE REFER |
| | TO THE PREVIOUS REVIEW COMMENT: |
| | 1A) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE |
| | DETECTORS ARE EXISTING OR PROPOSED TO BE INSTALLED. |
| | THERE IS A NOTE ON THE PLAN THAT SAY THERE SHALL BE |
| | SMOKE DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY |
| | PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315 |
| | WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR |
| | ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE |
| | SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. FBC-RESIDENTIAL 314 AND 315 |
| | |
| | 2) GFI PROTECTION SHALL BE INSTALLED AT ALL LOCATIONS |
| | INDICATED IN THE NEC 210.8. THE PLAN INDICATES GFI |
| | PROTECTION TO BE INSTALLED ONLY IN THE GARAGE, BATHROOM |
| | OR OUTDOORS. THE NEC 210.8 INDICATES ADDITIONAL |
| | LOCATION WHERE GFI PROTECTION IS REQUIRED, SPECIFICALLY |
| | (6) KITCHENS ? WHERE THE RECEPTACLES ARE INSTALLED TO |
| | SERVE THE COUNTERTOP SURFACES. (7) LAUNDRY, UTILITY, |
| | AND WET BAR SINKS ? WHERE THE RECEPTACLES ARE INSTALLED |
| | WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE SINK. |
| | NEC 210.8 |
| | |
| | 3) VERIFY #6 ROMEX ON 30AMP OCPD FOR DRYER CIRCUIT? |
| | REVISE AS NEEDED. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |