2015-05-27 12:50:285/27/2015
 PROJECT: SNED ADDITION
 PERMIT#: 15031318
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SMOKE DETECTORS TO BE INSTALLED IN ACCORDANCE WITH
 THE FBC-R 314, AND 315 THROUGHOUT THE DWELLING UNIT,
 NOT JUST THE RENOVATION. THE LOCATIONS INDICATED ON THE
 PLAN FOR THE INSTALLATION OF SMOKE DETECTORS ARE NOT
 REQUIRED ACCORDING TO THE FBC-R 314, 315. PLEASE REFER
 TO THE PREVIOUS REVIEW COMMENT:
 1A) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE
 DETECTORS ARE EXISTING OR PROPOSED TO BE INSTALLED.
 THERE IS A NOTE ON THE PLAN THAT SAY THERE SHALL BE
 SMOKE DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY
 PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315
 WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315
  
 2) GFI PROTECTION SHALL BE INSTALLED AT ALL LOCATIONS
 INDICATED IN THE NEC 210.8. THE PLAN INDICATES GFI
 PROTECTION TO BE INSTALLED ONLY IN THE GARAGE, BATHROOM
 OR OUTDOORS. THE NEC 210.8 INDICATES ADDITIONAL
 LOCATION WHERE GFI PROTECTION IS REQUIRED, SPECIFICALLY
 (6) KITCHENS ? WHERE THE RECEPTACLES ARE INSTALLED TO
 SERVE THE COUNTERTOP SURFACES. (7) LAUNDRY, UTILITY,
 AND WET BAR SINKS ? WHERE THE RECEPTACLES ARE INSTALLED
 WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE SINK.
 NEC 210.8
  
 3) VERIFY #6 ROMEX ON 30AMP OCPD FOR DRYER CIRCUIT?
 REVISE AS NEEDED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  