 PROJECT: SNED ADDITION
 PERMIT#: 15031318
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE DETECTORS
 ARE EXISTING OR PROPOSED TO BE INSTALLED. THERE IS A
 NOTE ON THE PLAN THAT SAY THERE SHALL BE SMOKE
 DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY
 PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315
 WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 2)THE SYMBOL LOCATED IN THE MEDIA ROOM FLOOR INDICATING
 A "FLOOR PLUG" SHALL BE INSTALLED USING MATERIALS
 LISTED SPECIFICALLY FOR THAT PURPOSE. SEE NEC 314.27(C)
 BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL BE
 USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C)
  
 3) VERIFY THE REQUIRED RECEPTACLE CIRCUIT FOR THE
 BATHROOM IS RATED 20AMP AND HAS NO OTHER OUTLETS. SEE
 NEC210.52(C)(3) IN ADDITION TO THE NUMBER OF BRANCH
 CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT
 LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. 210.52(C)(3) BATHROOM
 BRANCH CIRCUITS.
  
 4) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL
 SCHEDULE. WPB AMENDMENTS 107.3.5.1.2, AND 107.2.1.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  