| 2015-05-12 10:48:29 | 5/12/2015 |
| | PROJECT: SNED ADDITION |
| | PERMIT#: 15031318 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE DETECTORS |
| | ARE EXISTING OR PROPOSED TO BE INSTALLED. THERE IS A |
| | NOTE ON THE PLAN THAT SAY THERE SHALL BE SMOKE |
| | DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY |
| | PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315 |
| | WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR |
| | ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE |
| | SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 2)THE SYMBOL LOCATED IN THE MEDIA ROOM FLOOR INDICATING |
| | A "FLOOR PLUG" SHALL BE INSTALLED USING MATERIALS |
| | LISTED SPECIFICALLY FOR THAT PURPOSE. SEE NEC 314.27(C) |
| | BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL BE |
| | USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC |
| | 314.27(C) |
| | |
| | 3) VERIFY THE REQUIRED RECEPTACLE CIRCUIT FOR THE |
| | BATHROOM IS RATED 20AMP AND HAS NO OTHER OUTLETS. SEE |
| | NEC210.52(C)(3) IN ADDITION TO THE NUMBER OF BRANCH |
| | CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT |
| | LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO |
| | SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS |
| | SHALL HAVE NO OTHER OUTLETS. 210.52(C)(3) BATHROOM |
| | BRANCH CIRCUITS. |
| | |
| | 4) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL |
| | SCHEDULE. WPB AMENDMENTS 107.3.5.1.2, AND 107.2.1.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |