2015-04-30 09:50:55RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- DESIGNER OF RECORD TO PROVIDE ROOF FRAMING PLAN.
 SEC. 107.3.5.3(50 CITY AMENDMENTS. NOTE: PLAN SUBMITTED
 IS A TRAY LAYOUT ONLY NOT A DESIGN OF THE ROOF FRAMING
 SYSTEM. THE ROOF FRAMING SYSTEM IS DESIGNED BY THE
 DESIGNER OF RECORD.
  
 3- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF
 2010 FBC-RESIDENTIAL.
  
 4- DESIGNER OF RECORD TO REVIEW GEOTECHNICAL
 ENGINEERING EVALUATION FOR FOOTING SIZE
 RECOMMENDATIONS. SIZE OF FOOTINGS SPECIFIED BY THE
 DESIGNER OF RECORD ARE SMALLER ON ONE AREA. DESIGNER OF
 RECORD TO ACKNOWLEDGE REVIEW OF THE RECOMMENDATIONS AND
 ADDRESS ISSUE. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 5- TRUSS PACKAGE:
 A) ENGINEER NEEDS TO SIGN AND SEAL EACH TRUSS SHEET OR
 SIGN AND SEAL COMPLYING WITH ALL THE REQUIREMENTS OF
 SEC. 61G15-31.003 F.A.C. NOTE: INFORMATION SUBMITTED
 DOESN'T HAVE EVEN THE NAME OF THE TRUSS ENGINEER. NOTE:
 TRUSS PACKAGE MAY NOT NEED TO BE SUBMITTED NOW. IT MAY
 BE RENDERED TO THE BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
  
 B) DESIGNER OF RECORD TO APPROVE TRUSS PACKAGE PRIOR TO
 SUBMITTAL.
  
 6- ENERGY CALCULATIONS ARE TAKING THE CROSS VENTILATION
 CREDIT. PLANS TO PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. 405.6.4 OF
 2010 FBC-ENERGY CONSERVATION.
  
 7- NEW ADDITION SHOWS A NEW KITCHEN. CLARIFY WHAT'S
 HAPPENING WITH THE EXISTING KITCHEN. THERE IS NOT WORK
 SHOWN ON THE EXISTING KITCHEN. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- A) INFORMATION ON PLANS AND ENERGY CALCULATIONS NEED
 TO MATCH. COORDINATE AS REQUIRED. FOR EXAMPLE CHECK
 INSULATION IN CEILINGS AND WALLS (EXTERIOR AND
 ADJACENT). SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 NOTE: COORDINATE WITH ICYNENE ESR REPORT AND ICYNENE
 MANUFACTURER TECHNICAL INFORMATION SUBMITTED REGARDING
 R-VALUE AND ICYNENE THICKNESS.
  
 9- PROVIDE COPY OF CURRENT ICYNENE INSULATION ICC
 EVALUATION REPORT. ESR REPORT EXPIRED ON FEB 2013. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTORS OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $139,800.
 THE PERMIT FEE BALANCE IS $2943.92.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR:
 A) GARAGE DOOR SIZE AS SPECIFIED ON PLANS. PRODUCT
 APPROVAL SUBMITTED IS FOR 16 FEET WIDE DOORS. THERE IS
 A SEPARATE PRODUCT APPROVAL FOR SIZE SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS...
  