| 2016-02-16 12:15:12 | MECHANICAL PROVISOS: |
| | PERMIT #15031312 |
| | 333 DOWNTOWN |
| | 2/16/16 |
| | |
| | 1) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, |
| | AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING AND |
| | BALANCING IS REQUIRED IN ACCORDANCE WITH SECTION |
| | 503.2.9 FBC-10 ENERGY CONSERVATION. |
| | 503.2.9.1: AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING |
| | AND BALANCING. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT A WRITTEN |
| | BALANCE REPORT BE PROVIDED TO THE OWNER OR THE |
| | DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR |
| | HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED |
| | AREA EXCEEDING 5000 SQUARE FEET (465 M2). AIR |
| | DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND |
| | BALANCED BY A LICENSED ENGINEER OR A COMPANY OR |
| | INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A |
| | RECOGNIZED TESTING AND BALANCING AGENCY ORGANIZATION IN |
| | ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING |
| | STANDARDS. |
| | EXCEPTIONS: |
| | A) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES |
| | OF 15 TONS OR LESS PER SYSTEM MAY BE TESTED AND |
| | BALANCED BY A MECHANICAL CONTRACTOR LICENSED TO DESIGN |
| | AND INSTALL SUCH SYSTEM(S). |
| | B) BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES |
| | OF 65,000 BTU/H OR LESS PER SYSTEM ARE EXEMPT FROM THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 2) THE PERMIT IS BEING ISSUED WITHOUT APPROVED |
| | SUBMITTALS FOR MECHANICAL EQUIPMENT AND COMPONENTS |
| | INCLUDING ROOF TOP HVAC STANDS AND CURBS, EXTERIOR |
| | LOUVERS, FIRE AND FIRE/SMOKE DAMPERS, OUTSIDE AIR |
| | MOTORIZED DAMPERS, SMOKE DETECTORS, C0 AND NITROGEN |
| | DETECTORS, REFRIGERANT PIPING INSULATION, AC EQUIPMENT |
| | ETC. PLEASE REVIEW THE FOLLOWING: |
| | DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |