 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: DOORS LOCKED WITH MAGNETS ARE
 REQUIRED TO AUTOMATICALLY UNLOCK WITH AN OCCUPANT
 SENSOR. THE "PUSH TO EXIT" BUTTON CANNOT BE THE PRIMARY
 MEANS FOR RELEASING THE DOOR, IT MUST BE SECONDARY TO
 THE AUTOMATIC OCCUPANT SENSOR.
 REPEAT COMMENT - SHEET LS-7.0: BOTH SECONDARY EXITS
 FROM COMMON ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT
 THE EXIT ACCESS DOOR LEADING TO THE POOL DECK.
  