| Plan Review Notes For Permit 15031312 |
| Permit Number |
15031312 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-09-11 12:22:04 | 333 FERN STREET | | | PERMIT #15031312 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY | | | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE | | | (2012 EDITION WITH FLORIDA AMENDMENTS.) | | | | | | RESPONSE COMMENT - SINCE THIS BACKFLOW PREVENTER IS | | | LOCATED ON PRIVATE PROPERTY WPB UTILITIES DOES NOT HAVE | | | JURISDICTION. PER FLORIDA STATUTE 633 THE FIRE MARSHAL | | | IS RESPONSIBLE FOR ENFORCEMENT OF THE FIRE CODE; | | | THEREFORE, COMPLIANCE WITH THE COMMENT BELOW IS | | | REQUIRED. | | | ORIGINAL COMMENT - SHEET C-09: PER NFPA 24 SECTION | | | 6.2.1, BACKFLOW PREVENTER CONTROL VALVES SHALL BE | | | INSTALLED IN A FIRE-RATED ROOM ACCESSIBLE FROM THE | | | EXTERIOR. | | | | | | SHEET LS-7.0: THE COOKING GRILL LOCATED ON THE POOL | | | DECK SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT | | | LEAST 10 FEET FROM ANY BUILDING, STRUCTURE, OR | | | COMBUSTIBLES PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL | | | WILL BE USED UNDER A ROOF STRUCTURE, THE DESIGN SHALL | | | COMPLY WITH NFPA 96. | | | | | | REPEAT COMMENT - SHEET LS-7.0: BOTH SECONDARY EXITS | | | FROM COMMON ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT | | | THE EXIT ACCESS DOOR LEADING TO THE POOL DECK. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | | | | | | | | | | |
|