Notes
Date Text
2015-09-11 12:22:04333 FERN STREET
 PERMIT #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 RESPONSE COMMENT - SINCE THIS BACKFLOW PREVENTER IS
 LOCATED ON PRIVATE PROPERTY WPB UTILITIES DOES NOT HAVE
 JURISDICTION. PER FLORIDA STATUTE 633 THE FIRE MARSHAL
 IS RESPONSIBLE FOR ENFORCEMENT OF THE FIRE CODE;
 THEREFORE, COMPLIANCE WITH THE COMMENT BELOW IS
 REQUIRED.
 ORIGINAL COMMENT - SHEET C-09: PER NFPA 24 SECTION
 6.2.1, BACKFLOW PREVENTER CONTROL VALVES SHALL BE
 INSTALLED IN A FIRE-RATED ROOM ACCESSIBLE FROM THE
 EXTERIOR.
  
 SHEET LS-7.0: THE COOKING GRILL LOCATED ON THE POOL
 DECK SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT
 LEAST 10 FEET FROM ANY BUILDING, STRUCTURE, OR
 COMBUSTIBLES PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL
 WILL BE USED UNDER A ROOF STRUCTURE, THE DESIGN SHALL
 COMPLY WITH NFPA 96.
  
 REPEAT COMMENT - SHEET LS-7.0: BOTH SECONDARY EXITS
 FROM COMMON ROOM 701.01 HAVE CARD READERS (KEY/TOOL) AT
 THE EXIT ACCESS DOOR LEADING TO THE POOL DECK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  
  