| Date |
Text |
| 2016-02-17 18:24:51 | 2010 FLORIDA BUILDING CODE W/ 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS |
| | ADOPTED APRIL 25/2013. |
| | |
| | ***PROVISOS*** |
| | ***ISSUED AT CONTRACTOR'S RISK*** |
| | |
| | 1. DELEGATED ENGINEERING: HORIZONTAL TRELLIS FOUND ON |
| | THE SOUTH & WEST SIDES OF THE BUILDING (SEE SECTION 6, |
| | 8 & 9 PAGE A7.5.4). PLEASE SHOW WIND DESIGN AND |
| | ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 2. THE LETTER FROM JOE CUSCHIERI P. E. ACOUSTICS AND |
| | VIBRATION CONSULTANT HAS SUBMITTED A RATIONAL ANALYSIS |
| | AS TO HOW THEY ARE ACHIEVING THE IIC AND STC RATINGS. |
| | ALL FLOORS (FLOOR SLABS ARE 8 INCH POST TENSION SLABS) |
| | THE 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | |
| | DEFERRED SUBMITTALS. 107.3.4.2. SUBMIT STC, IIC, AND |
| | FLAME SPREAD TEST REPORTS (REVIEWED BY DOR) PRIOR TO |
| | INSTALLATION OF FLOORING UNDERLAYMENT. |
| | (A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | (B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | (C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200 |
| | (TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723). |
| | |
| | 3. PROVISO: NOTE THERE IS NO KNOWING WHICH WAY A R2 |
| | OCCUPANCY CAN TURN INTO EITHER AN APARTMENT BUILDINGS |
| | ARE AN R-2 AS WELL AS CONDOMINIUMS. IT ISN?T UNTIL C.O. |
| | THAT THE DOCUMENTS GO TO THE STATE FOR THE DECLARATION |
| | OF CONDOMINIUM. THIS NEXT CODE ISSUE WILL BE A PROVISO, |
| | THE PLANS BEING REVIEWED AS THIS IS TO BE A CONDOMINIUM |
| | AND UNDER FAIR HOUSING. |
| | PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER |
| | THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY |
| | REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, |
| | NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE |
| | WATER INTO THE POOL. ON THE OTHER HAND IF THE |
| | ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL, |
| | AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE |
| | PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO |
| | MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE |
| | ACCESSIBILITY CODE POOL LIFTS. |
| | |
| | 4. THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C |
| | STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT |
| | REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM |
| | THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT |
| | CONCRETE ROOF. |
| | |
| | 5. PRODUCT APPROVALS: DEFERRED SUBMITTAL. ARCHITECT |
| | WILL REVIEW/ APPROVE/ STAMP EACH PRODUCT APPROVAL W/ |
| | SHOP DRAWING STAMP BEFORE SUBMISSION TO CITY BUILDING |
| | DEPARTMENT. |
| | |
| | 6. A7.5.3, PROVISO: NOTE: THE POOL TRELLIS STRUCTURE |
| | (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE |
| | DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE |
| | REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7. PAGE 136 A7.5.4. PROVISO: DETAIL # 5 RIGID ALUMINUM |
| | CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND DESIGN |
| | CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 . ALSO: |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 8. FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 909. |
| | |
| | 9. PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION |
| | SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS |
| | SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED |
| | STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH |
| | FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| | ARE LOCKED. |
| | |
| | 10. FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY |
| | REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET |
| | (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| | VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND |
| | 1022.9. |
| | |
| | 11. THE POOL AND SPA PLANS HAVE NOT BEEN REVIEWED. A |
| | SEPARATE PERMIT WITH SEPARATE APPLICATIONS, PLANS, FEES |
| | AND REVIEWS REQUIRED. |
| | |
| | 12. SEE FIRE DEPARTMENT PROVISO/REDLINES ON SHEETS |
| | LS7.0 AND LS8.0. |
| | |
| | |
| | |