| Date |
Text |
| 2015-12-02 18:52:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF |
| | THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | PG. E2.1.1 |
| | 1. REAR MAIN LOBBY DOOR INTO VEHICULAR AREA MAY BE |
| | MISSING AN EXIT LIGHT. |
| | 2. NO EXIT LIGHTS IN THE VEHICULAR AREA. |
| | 3. EXIT LIGHT MISSING AT DOOR IN ROOM 136 TO PARKING |
| | AREA. |
| | 4. NEC 408.4(B) SHOW LOCATION OF SOURCE OF POWER AND |
| | DISCONNECT. ALL SWITCHBOARDS SHALL BE MARKED TO |
| | INDICATE ORIGIN OF POWER. |
| | PG. E2.2.1 |
| | 1. FBC-B SECTION 1011.1 EXIT SIGN PLACEMENT SHALL BE |
| | SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS. |
| | 2. BIKE STG. ROOM 209 MISSING AUTOMATIC LIGHTING |
| | CONTROL |
| | PG. E2.3.1, E2.4.1, E2.5.1, E2.6.1 |
| | 1. FBC-B SECTION 1011.1 EXIT SIGN [PLACEMENT SHALL BE |
| | SUCH THAT THERE IS NO MORE THAN 100 FT. BETWEEN SIGNS. |
| | PG. E2.7.1 |
| | 1. NEC 406.8(B) ALL 15 AND 20 AMP 125 TO 250 VOLT |
| | NON-LOCKING RECEPTACLES INSTALLED IN WET LOCATIONS |
| | SHALL BE RATED WEATHER RESISTANT ?WR?. (TYPICAL FOR ALL |
| | OUTDOOR RECEPTACLES). |
| | 2. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM |
| | BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT. |
| | PG. E2.8.1 |
| | 1. RELOCATE THIS TOWARDS CORNER TO MAKE IT VISIBLE FROM |
| | BOTH DIRECTIONS AND TO POINT TOWARDS THE ACTUAL EXIT. |
| | PG. E2.9.1 |
| | 1. ADDITIONAL NOTE TO BE ADDED #7: NEC 406.8(B) ALL 15 |
| | AND 20 AMP 125 TO 250 VOLT NON-LOCKING RECEPTACLES |
| | INSTALLED IN WET LOCATIONS SHALL BE RATED WEATHER |
| | RESISTANT ?WR?. (TYPICAL FOR ALL OUTDOOR RECEPTACLES). |
| | PG. E2.10.1 |
| | 1. SHOW PANEL ?REL? ON RISER DIAGRAM AND PANEL |
| | SCHEDULES. |
| | PG. E4.1.1 |
| | 1. FOLLOWING THE LOADS FROM BOTH, SWITCHBOARDS 1 & 2, |
| | THERE ARE SEVERAL PANELS WHICH DO NOT APPEAR ON THE |
| | RISER DIAGRAM. |
| | PG. E4.3.1 |
| | 1. THE POWER SOURCE FOR PANEL ?RB? IS NOT IDENTIFIED, |
| | OR REFLECTED ON THE RISER DIAGRAM. |
| | PG. E5.1.1 |
| | 1. CIRCUIT DIRECTORY/PANEL SCHEDULE FOR PANEL ?RLB? IN |
| | NOT INDICATED AMONG THE PANEL SCHEDULES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH. |
| | PH. :(561) 805-6746 |