| 2015-12-12 09:31:31 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 3RD REVIEW |
| | DATE: SEPT. DEC.12 /2015 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC |
| | PLACES ORDINANCE. |
| | 2-6 COMPLIED. |
| | 7A-7I) COMPLIED. |
| | |
| | 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS |
| | FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE |
| | SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN |
| | AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 7K-7P) COMPLIED. |
| | |
| | 8-10) COMPLIED. |
| | |
| | 11A-B) COMPLIED |
| | |
| | 11C), COMPLIED/ PROVISO. THE LETTER FROM JOE CUSCHIERI |
| | P. E. ACOUSTICS AND VIBRATION CONSULTANT HAS SUBMITTED |
| | A RATIONAL ANALYSIS AS TO HOW THEY ARE ACHIEVING THE |
| | IIC AND STC RATINGS. |
| | ALL FLOORS (FLOOR SLABS ARE 8 INCH POST TENSION SLABS) |
| | , THE 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | |
| | PROVISO: DEFERRED SUBMITTALS. 107.3.4.2. |
| | 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 11D) COMPLIED. |
| | |
| | 12A-D) COMPLIED. |
| | |
| | 12E) PROVISO: NOTE THERE IS NO KNOWING WHICH WAY A R2 |
| | OCCUPANCY CAN TURN INTO EITHER AN APARTMENT BUILDINGS |
| | ARE AN R-2 AS WELL AS CONDOMINIUMS. IT ISN?T UNTIL C.O. |
| | THAT THE DOCUMENTS GO TO THE STATE FOR THE DECLARATION |
| | OF CONDOMINIUM. THIS NEXT CODE ISSUE WILL BE A PROVISO, |
| | THE PLANS BEING REVIEWED AS THIS IS TO BE A CONDOMINIUM |
| | AND UNDER FAIR HOUSING. |
| | PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER |
| | THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY |
| | REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, |
| | NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE |
| | WATER INTO THE POOL. ON THE OTHER HAND IF THE |
| | ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL, |
| | AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE |
| | PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO |
| | MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE |
| | ACCESSIBILITY CODE POOL LIFTS. |
| | |
| | 12F-G) COMPLIED. |
| | |
| | . |
| | 13) COMPLIED. |
| | |
| | 14A-D) COMPLIED. |
| | |
| | 14E) PROVISO: THE PLANS INDICATE THE USE OF |
| | PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED |
| | CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7, |
| | THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE |
| | THE LIGHTWEIGHT CONCRETE ROOF. |
| | |
| | 15) COMPLIED, |
| | |
| | 16) PROVISO:) PRODUCT APPROVALS: DEFERRED SUBMITTAL. |
| | ARCHITECT WILL REVIEW/ APPROVE/ STAMP EACH PRODUCT |
| | APPROVAL W/ SHOP DRAWING STAMP BEFORE SUBMISSION TO |
| | CITY BUILDING DEPARTMENT.. |
| | |
| | 17-18) COMPLIED. |
| | |
| | 19)A7.5.3 |
| | 19A) PROVISO: NOTE: THE POOL TRELLIS STRUCTURE |
| | (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE |
| | DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE |
| | REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 19B) COMPLIED. |
| | |
| | 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID |
| | ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND |
| | DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 . |
| | ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 21-23) COMPLIED. |
| | |
| | 24 A-C) COMPLIED. |
| | |
| | 24D) COMPLIED. FBC-B 403.4.6 SMOKE REMOVAL. SMOKE |
| | CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 909. SEE MECHANICAL REVIEWERS COMMENTS. |
| | |
| | 24E-G) COMPLIED. |
| | |
| | 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION |
| | SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS |
| | SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED |
| | STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH |
| | FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| | ARE LOCKED. |
| | |
| | 24I) COMPLIED. FBC-B 403.5.4 SMOKEPROOF EXIT |
| | ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS |
| | MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF |
| | FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH |
| | SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER |
| | COMMENT 9A. |
| | |
| | 24J) COMPLIED |
| | |
| | 24K) COMPLIED. |
| | |
| | 25) COMPLIED. IMPACT FEES PAID. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |