| 2015-09-10 12:50:25 | PLUMBING: |
| | 1) SHT.A6.2.1 - IDENTIFIES THE UNITS AS 303/503 & |
| | 304/504 IN THE BOTTOM RIGHT HAND CORNER OF THE PLAN BY |
| | THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS |
| | LABELED AS UNITS 302/502. CLARIFY |
| | 2) SHT. A 6.3.1 - IDENTIFIES THE UNITS AS 305/505 & |
| | 306/506 IN THE LOWER RIGHT HAND CORNER OF THE PLAN BY |
| | THE DRAWING NUMBER BUT DETAILS #1 & #2 HAVE THE UNITS |
| | LABELED AS 303/503. CLARIFY. |
| | 3) SHT.A 6.10.1 - SHOW THE LENGTH OF THE WING WALL |
| | ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE |
| | WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA |
| | GUIDELINES. |
| | 4) SHT. A 6.11.1 -SHOW THE LENGTH OF THE WING WALL |
| | ADJACENT TO THE WATER CLOSET IN THE MASTER BATH. THE |
| | WING WALL SHALL NOT EXCEED 24 INCHES PER THE FHA |
| | GUIDELINES. |
| | 5) SHT. A 6.15.1 - SHOW THE LENGTH OF THE SHOWER WALL |
| | ADJACENT TO THE WATER CLOSET IN THE MASTER BATH.THE |
| | MEASUREMENT SHALL BE TAKEN FROM THE FACE OF THE WALL |
| | BEHIND THE WATER CLOSET TO THE OFFSET. THIS CANNOT |
| | EXCEED 24 INCHES. |
| | 6) SHT. P 2.1.1 - THE NOTE AT THE GENERATOR REFERS TO |
| | "P6-02" - WHAT IS THIS? THERE IS NO SUCH DRAWING IN THE |
| | PLAN. CLARIFY. |
| | 7) SHT. P 4.1.8. - THERE IS A HORIZONTAL STORM DRAIN |
| | LINE FROM 2-4" DD'S ( 940 SQ. FT.& 950 SQ. FT.) ON THE |
| | 7TH FLOOR DISCHARGING A TOTAL OF 1890 SQUARE FEET. THE |
| | HORIZONTAL LINE IS NOT SIZED BUT THIS LINE NEEDS TO BE |
| | A MINIMUM OF 5". THE MAXIMUM SQUARE FOOTAGE A 4" |
| | HORIZONTAL STORM DRAIN CAN CARRY AT A 5" DESIGN |
| | RAINFALL RATE IS 1504 SQUARE FEET. THIS SECTION NEEDS |
| | TO BE INCREASED TO A MINIMUM SIZE OF 5 INCH. |
| | 8) SHT. P 5.1.2. - ELEVATOR SUMP DETAIL - A FULL OPEN |
| | GATE VALVE IS REQD. ON THE DOWNSTREM (DISCHARGE) SIDE |
| | OF THE CHECK VALVE PER 2010 FBC-PLUMBING SEC.712.2. |
| | 9) SUBMIT SPECIFICATIONS FOR THE TANKLESS WATER HEATER. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) THE DETAIL FOR THE WATER HEATER & RELIEF VALVE |
| | DISCHARGE ON SHT.P5.1.2 MEETS CODE BUT THE RISERS ON |
| | SHT.P4.1.10 STILL SHOW THE RELIEF LINES & PAN DRAINS |
| | INTO THE SAME RISER. PLACE A NOTE ON P4.1.10 TO SEE |
| | SHT. P5.1.2 FOR RELIEF VALVE & PAN DRAIN DETAIL. |
| | |
| | SWIMMING POOL & SPA |
| | 1) INDICATE ON THE PLAN HOW THE OCCUPANT LOAD OF 31 |
| | PERSONS FOR THE POOL WAS CALCULATED.WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1. |
| | 2) THE POOL & SPA PLANS SHOW THE WASTE WATER |
| | DISCHARGING TO THE SANITARY SYSTEM. SEE SHEET #367, |
| | POOL 4 OF 4 & SHT.370 SPA 2. POOL WATER CANNOT |
| | DISCHARGE TO THE SANITARY OR TO THE STORM SYSTEM PER |
| | CITY ORDINANCE SEC.90-126 (5) AND SEC. 90-203 (A) , |
| | 90-204, 90-205 (1). |
| | 3) THE MAXIMUM FILTRATION RATE IN GALLONS PER MINUTE |
| | PER SQUARE FOOT OF FILTER AREA SHALL BE 0.075 FOR |
| | CARTRIDGE FILTERS PER 2010 FBC SEC.424.1.6.5.5. |
| | INDICATE COMPLIANCE ON THE PLANS FOR BOTH THE POOL & |
| | SPA. |
| | 4) SUBMIT VERIFICATION FROM THE PALM BEACH COUNTY |
| | HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING |
| | PERMIT HAS BEEN SUBMITTED TO THEM FOR THIS POOL & SPA. |
| | 5) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES |
| | WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FROM THE |
| | SYSTEM SHALL BE PROVIDED PER 2010 FBC SEC.424.1.6.5.14. |
| | SEE RETURN LINE ON THE POOL & SPA. |
| | 6) THE CAPACITY OF THE COLLECTOR TANKS SHALL BE AT |
| | LEAST 1 MINUTE OF OF THE RECIRCULATED FLOW PER 2010 FBC |
| | SEC.424.1.6.5.10.5. PLEASE EXPLAIN THE METHOD OF |
| | ARRIVING AT THE REDUCED SIZE OF THE COLLECTOR TANKS FOR |
| | THE POOL & SPA.. |
| | 7) SIZE ALL THE PIPING TO AND FROM THE POOL HEATERS ON |
| | THE POOL AND SPA PIPING RISERS.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) SUBMIT MSDS DOCUMENTS FOR THE POOL CHEMICALS.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 9) INDICATE THE LOCATION OF THE CHEMICALS ON THE POOL, |
| | SPA AND BUILDING PLANS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT.370 (SPA 2) SHOWS 50 GAL. ACID & CHLORINE TANKS |
| | SHARED WITH POOL AND SHT. 367 (POOL 4) SHOWS 30 GAL. |
| | ACID & CHLORINE TANKS.ARE THESE TWO SEPARATE SETS OF |
| | TANKS OR SHARED AND WHAT IS THE PROPER CAPACITY? |
| | CLARIFY. |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | HEATERS. THE HEATERS SHALL BE LISTED AND LABELED IN |
| | ACCORDANCE WITH 2010 FBC-FUEL GAS SEC. 301.3. |
| | 12) SUBMIT MANUFACTURER'S SPECIFICATIONS OF RTHE MAIN |
| | DRAIN GRATES FOR THE POOL AND SPA.WPB AMEND. TO FBC |
| | SEC. 107.2.1, ANSI/APSP-7 SEC.4.5. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | REVIEW NOT COMPLETE |