| Date |
Text |
| 2015-10-01 20:13:37 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF |
| | THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. THESE BEING RENTAL UNITS, THE CORRIDOR OUTLETS ARE |
| | UNDER THE HOUSE LOAD AND THUS WILL NOT PLACE A BURDEN |
| | ON ANOTHER TENANT. (RENTAL OR PRIVATE OWNERSHIP OF |
| | THESE UNITS HAD NOT BEEN MADE KNOW BEFORE) |
| | 2. NEC REQUIRES THAT YOU INCLUDE A LAUNDRY CIRCUIT IN |
| | THE LOAD CALCS. THE OTHER GENERAL PURPOSE OUTLETS WHICH |
| | MAY BE IN THE LAUNDRY ROOM/AREA FALL UNDER THE GENERAL |
| | LIGHTING LOADS. THERE IS NOTHING PROHIBITING YOU FROM |
| | DOING IT THE WAY YOU HAVE, IT IS JUST NOT NECESSARY. |
| | 3. THERE APPEARS NOT TO BE ENOUGH LIGHT TO WORK INSIDE |
| | THE ELECTRICAL PANEL COMING FROM THE DOWN LIGHTS IN THE |
| | KITCHEN ISLAND, ON PG. E3.8.1, PG. E3.9.1, PG. E3.9.1A |
| | 4. PG. E3.16 CLUB HOUSE: MISSING CONVENIENCE GFI |
| | OUTLETS AT ISLAND COUNTER. |
| | 5. PG. E3.16 CLUB HOUSE: PER NEC 422.52 ELECTRIC |
| | DRINKING FOUNTAINS SHALL BE ON A GFI PROTECTED CIRCUIT. |
| | 6. PG. E3.16 CLUB HOUSE: INDICATE WHICH SIDE THE PANEL |
| | WILL FACE. PER NEC 210.70(3) THERE HAS TO BE AMPLE |
| | LIGHTING ABOUT THE ELECTRICAL PANEL. |
| | 7. PG. E3.16 CLUB HOUSE: I DON?T SEE THE MANDATORY |
| | ADDITIONAL CONTROLS (OCCUPANCY SENSORS) REQUIRED BY THE |
| | FBC-ENERGY FOR THIS AREA. |
| | 8. (CHECK THE EXIT DOOR BY THE RESTROOMS FOR THE PROPER |
| | SWING IN THE PATH OF TRAVEL.) |
| | 9. PG. E4.1.1 PANEL G HAS A CALCULATED LOAD OF 156 AMP |
| | WITHOUT TAKING 125% FOR THE CONTINUOUS LOADS INTO |
| | ACCOUNT; #4 THWN AL IS ONLY GOOD FOR 150 AMP. |
| | 10. PG. E4.2.1 PANEL MEL HAS A LOAD OF 11.6 AMP NOT |
| | 8.8. |
| | 11. PG. E4.3.1 PANEL RL HAS A CONNECTED LOAD OF 820 AMP |
| | ACCORDING TO YOU NUMBERS, HAVE YOU CONSIDERED THE |
| | CONTINUOUS LOADS AS THE FEEDERS ARE EXACT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |