| 2015-09-28 15:40:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: MON. SEPT. 28 /2015 |
| | ACTION: DENIED |
| | |
| | 1) PROVISO: ; THE CITY OF WEST PALM BEACH ART IN PUBLIC |
| | PLACES ORDINANCE. |
| | 2-6 COMPLIED. |
| | 7A-7I) COMPLIED. |
| | 7J) PROVISO/ DELEGATE ENGINEER. ) HORIZONTAL TRELLIS |
| | FOUND ON THE SOUTH & WEST SIDES OF THE BUILDING SEE |
| | SECTION 6,8 & 9 PAGE A7.5.4. PLEASE SHOW WIND DESIGN |
| | AND ANCHORING DETAILS. FBC-B 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | 7K-7M) COMPLIED. |
| | 7N) 2ND REQUEST. RESPONSE INDICATES NOTE # 37 SHEET |
| | 024-LS-1.0. NO SUCH NOTE. NOR ON SHEET 023-LS-01. |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| | 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION |
| | EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER. |
| | ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, |
| | SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, |
| | SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR |
| | THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED |
| | TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT |
| | LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS, |
| | PERMANENTLY INSTALLED AND READILY VISIBLE |
| | 70-7P) COMPLIED. |
| | 8A-B) COMPLIED. |
| | 9A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE |
| | INDICATED THE DIMENSIONS WERE ADDED TO SHEETS |
| | 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED |
| | ON SHEETS 038-A2.3.1 OR 039- A2.3.2. |
| | DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON |
| | AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT. |
| | THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE |
| | LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3. |
| | USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD |
| | APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE |
| | IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY |
| | DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL |
| | DWELLING UNITS. |
| | (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| | AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| | THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| | 9B) COMPLIED. |
| | 10A-B) COMPLIED. |
| | 10C) NEW COMMENT. PLEASE SEE MARK UP ON SHEET |
| | 039-A2-3-2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE |
| | CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM |
| | IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING |
| | AND THE 2010 FBC-B 1018.2 EXC. # 2. |
| | 11A) DISCREPANCY IN PLANS, SEMI-COMPLIED. THE RESPONSE |
| | INDICATED THE DIMENSIONS WERE ADDED TO SHEETS |
| | 077-A6.1.1 AND 078-A6.1.2 BUT THEY WERE NEVER CHANGED |
| | ON SHEETS 045-A2.5.2. |
| | DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED COMMON |
| | AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE UNIT. |
| | THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON THE |
| | LATCH SIDE OF THE DOOR, PER FAIR HOUSING REQUIREMENT 3. |
| | USABLE DOORS. GUIDELINE SECTION 100.205(C)(2) WOULD |
| | APPLY TO DOORS THAT ARE A PART OF AN ACCESSIBLE ROUTE |
| | IN THE PUBLIC AND COMMON USE AREAS OF MULTIFAMILY |
| | DWELLINGS AND TO DOORS INTO AND WITHIN INDIVIDUAL |
| | DWELLING UNITS. |
| | 11B) COMPLIED. |
| | 11C), 11C)(1A), 11C(1B) 11C)(1C) THE LETTER FROM JOE |
| | CUSCHIERI P. E. ACOUSTICS AND VIBRATION CONSULTANT WILL |
| | NEED TO PROVIDE RATIONAL ANYLSIS AS TO HOW THEY ARE |
| | ACHIEVING THE IIC AND STC RATINGS STATED WITHIN THE |
| | LETTER. WE SEE MANY PRODUCTS THAT WERE TESTED IN |
| | LAVATORIES ON A 6 INCH CONCRETE SLAB AND BARELY GET A |
| | IIC RATING OF 51 WITH SOUND INSULATION. AT THE VARY END |
| | OF THE LETTER THE STATEMENT FOR HARD FINISHES SUCH AS |
| | WOOD OR MARBLE OR TILE MITIGATION FOR STRUCTURE BORNE |
| | SOUND SUCH AS THE USE OF KINETIC SR FLOOR BOARD OR |
| | EQUIVALENT SHOULD BE CONSIDERED TO MEET THE FBC |
| | REQUIREMENT. |
| | COMMENT FROM THE 1ST REVIEW. 11C) THIS COMMENT WILL BE |
| | A COMMON COMMENT FOR ALL FLOORS (FLOOR SLABS ARE 8 INCH |
| | POST TENSION SLABS) , THE 3RD -16TH STORY. PLEASE |
| | PROVIDE COMPLIANCE WITH BLDG TYPE: TYPE I/ TYPE II |
| | FLOOR INSULATION |
| | |
| | 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 11D) NEW COMMENT. PLEASE SEE MARK UP ON SHEET |
| | 045-A2.5.2. THE COMMON CORRIDOR HAS PINCH POINTS IN THE |
| | CORRIDOR NEXT TO THE COLUMN LINE WHERE 36 INCH MINIMUM |
| | IS REQUIRED FOR THE CORRIDOR WIDTH BOTH BY FAIR HOUSING |
| | AND THE 2010 FBC-B 1018.2 EXC. # 2. |
| | |
| | 12A) COMPLIED. |
| | |
| | 12B) POOL DECK AND THE MEANS OF EGRESS. PLEASE VERIFY |
| | THE EGRESS DOORS THAT LEAD FROM THE POOL DECK TO THE |
| | INTERIOR OF THE BUILDING HAVE CARD READERS ON BOTH |
| | DOORS. PLEASE VERIFY THE CARD READERS ARE FOR ENTRY |
| | ONTO THE POOL DECK. THAT IF YOU ARE ON THE POOL DECK |
| | THE DOORS WILL AUTOMATICALLY UNLOCK. THIS CONFIGURATION |
| | WILL ALSO LIMIT CHILDREN GAINING ACCESS TO THE POOL |
| | DECK AND BE IN COMPLIANCE WITH 2010 FBC-B 424.1.3.1.9. |
| | |
| | 12C) COMPLIED. |
| | |
| | 12D) 2ND REQUEST. PLEASE SEE THE SHEET 119-A6.16.1 THE |
| | TOTAL CORRIDOR WIDTH IS 4 FT. 7 ? INCHES WIDE. DOOR |
| | 706F DOES NOT COMPLY WITH THE FAIR HOUSING GUIDE LINES |
| | REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| | USE AREAS. ANSI A117.1 TABLE 404.2.4.1 MANEUVERING |
| | CLEARANCES FOR MANUAL SWING DOORS. |
| | |
| | 12E) NOTE THERE IS NO KNOWING WHICH WAY A R2 OCCUPANCY |
| | CAN TURN INTO. APARTMENT BUILDINGS ARE A R-2 AS WELL AS |
| | CONDOMINIUMS. IT ISN?T UNTIL C.O. THAT THE DOCUMENTS GO |
| | TO THE STATE FOR THE DECLARATION OF CONDOMINIUM. THIS |
| | NEXT CODE ISSUE WILL BE A PROVISO, THE PLANS BEING |
| | REVIEWED AS THIS IS TO BE A CONDOMINIUM AND UNDER FAIR |
| | HOUSING. |
| | PROVISO: NOTE THIS POOL DECK AND POOL ARE COVERED UNDER |
| | THE FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY |
| | REQUIRES ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, |
| | NOT AN ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE |
| | WATER INTO THE POOL. ON THE OTHER HAND IF THE |
| | ASSOCIATION ELECTS TO ALLOW THE COMMUNITY ROOM, POOL, |
| | AND OR POOL DECK TO BE RENTED OUT FOR PARTIES THAT THE |
| | PUBLIC COULD USE, THEN THIS AREA WOULD BE REQUIRED TO |
| | MEET FLORIDA ACCESSIBILITY SECTION 1009 OF THE |
| | ACCESSIBILITY CODE POOL LIFTS. |
| | |
| | 12F) 2ND REQUEST. ) THIS NOTE WILL BE A COMMON NOTE FOR |
| | FLOORS 7-20TH FLOORS. THE DOOR SCHEDULE FOUND ON PAGE |
| | 126 A.7.1.1 (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE |
| | ARE VARIOUS DOORS IN THE CORRIDOR(STORAGE & ELECTRICAL) |
| | THAT STATE THAT A FIRE DAMPER IS TO BE INSTALLED IN THE |
| | LOUVERED DOOR. PLEASE SHOW COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE |
| | DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY. |
| | THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE |
| | PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED |
| | WITHIN THE LOUVERED DOOR. |
| | |
| | 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS |
| | OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE |
| | DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| | |
| | 12G) COMPLIED. |
| | 13A) COMPLIED. SLIDING GLASS DOORS. |
| | 13B) 2ND REQUEST. ) FOR ALL SLIDING GLASS DOORS THE |
| | HARDWARE WILL ALSO NEED TO MEET THE ANSI 117.1 STANDARD |
| | 404.2.7. RESPONSE INDICATES SEE SPECS, REQUIREMENT |
| | INCLUDED IN SPEC. IF SPEC BOOKS ARE SUBMITTED WE STAMP |
| | THEM VOID. WE ARE LOOKING FOR CODE COMPLIANCE ON THE |
| | PLANS. WE DO NOT REVIEW SPEC BOOKS> |
| | |
| | 14A-D) COMPLIED. |
| | |
| | 14E) PROVISO: THE PLANS INDICATE THE USE OF |
| | PRE-ENGINEERED A/C STANDS. WHEN FIGURING THE REQUIRED |
| | CLEARANCES IN HEIGHT REQUIRED BY TABLE FBC-B 1509.7, |
| | THE CLEARANCE IS FROM THE FINISHED ROOF HEIGHT, ABOVE |
| | THE LIGHTWEIGHT CONCRETE ROOF. |
| | |
| | 15) COMPLIED, |
| | |
| | 16A-C) PRODUCT APPROVALS: DEFERRED SUBMITTAL. ARCHITECT |
| | WILL APPROVE/ STAMP EACH PRODUCT APPROVAL AND SUBMIT. |
| | |
| | 17-18) COMPLIED. |
| | |
| | 19)A7.5.3 |
| | 19A) PROVISO: ) NOTE: THE POOL TRELLIS STRUCTURE |
| | (PERGOLA) THIS DETAIL INDICATES IT IS GOING TO BE |
| | DESIGNED BY A SPECIALTY ENGINEER. BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT, THE PLANS WILL NEED TO BE |
| | REVIEWED BY THE ENGINEER OF RECORD. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 19B) COMPLIED. |
| | |
| | |
| | |
| | 20) PAGE 136 A7.5.4. 20A) PROVISO: DETAIL # 5 RIGID |
| | ALUMINUM CANOPY WITH FABRIC WRAPPED WILL REQUIRE WIND |
| | DESIGN CRITERIA SEE OPTIONS FOUND UNDER FBC-B 3105.4 . |
| | ALSO: FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 21-23) COMPLIED. |
| | |
| | 24 A-C) COMPLIED. |
| | |
| | 24D) 2ND REQUEST ) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE |
| | CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 909. SEE MECHANICAL REVIEWERS COMMENTS. |
| | |
| | 24E-G) COMPLIED. |
| | |
| | 24H) PROVISO: FBC-B 403.5.3.1 STAIRWAY COMMUNICATION |
| | SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS |
| | SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED |
| | STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH |
| | FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| | ARE LOCKED. |
| | |
| | 24I) 2ND REQUEST. ) FBC-B 403.5.4 SMOKEPROOF EXIT |
| | ENCLOSURES. EVERY REQUIRED EXIT STAIRWAY SERVING FLOORS |
| | MORE THAN 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF |
| | FIRE DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH |
| | SECTIONS 909.20 AND 1022.9. SEE MECHANICAL REVIEWER |
| | COMMENT 9A. |
| | |
| | 24J) 2ND REQUEST, RESPONSE: ACKNOWLEDGED. FBC-B 1022.8 |
| | FLOOR IDENTIFICATION SIGNS. / 1022.8.1 SIGNAGE |
| | REQUIREMENTS. |
| | |
| | 24K) COMPLIED. |
| | |
| | 25) COMPLIED. IMPACT FEES PAID. |
| | |
| | 26) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |