| 2015-05-28 16:34:56 | THE ELECTRICAL REVIEW FAILED AS INDICATED ON THE |
| | ATTACHED DOCUMENT. A COPY OF MY NOTES HAS BEEN EMAILED |
| | TO DESIGN PROFESSIONAL AS WELL. |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE |
| | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH |
| | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN |
| | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE |
| | DIGITAL PLANS. |
| | |
| | PAGE E1.0.0 LEGEND & NOTES |
| | 1. LIGHTING FIXTURE NOTES: CORRECT NOTE 1 TO INDICATE |
| | THE PROPER CODE SECTION ADDRESSING LUMINAIRE SUPPORT. |
| | 2. GENERAL NOTES: CORRECT NOTE 10 TO COMPLY WITH |
| | CURRENT FBC REQUIREMENTS FOR FIRE SEALING AS NOTED. |
| | 3. OUTDOOR & LANDSCAPE NOTES: CORRECT NOTE 4 TO INCLUDE |
| | THE REQUIREMENT OF NEC 406.8 (B) |
| | 4. A NOTE REQUIRING COMPLIANCE WITH NEC 406.11 |
| | TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS. IN ALL |
| | AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15 AND |
| | 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER RESISTANT |
| | RECEPTACLES. |
| | 5. YOU WILL NOTICE THAT ON EVERY FLOOR I HAVE MADE A |
| | NOTATION AS TO THE REQUIRED SERVICE OUTLET FOR THE |
| | INDIVIDUAL UNIT A/C EQUIPMENT IN A CLOSET IN THE COMMON |
| | CORRIDOR. AS A MATTER OF MY REVIEW, I HAVE MEASURED THE |
| | DISTANCES OF THE OUTLETS IN THE CORRIDORS AND THEY DO |
| | COMPLY WITH THIS REQUIREMENT BUT WILL THE BLDG. ALLOW |
| | THE INDIVIDUAL UNIT OWNERS TO USE THESE OUTLETS FOR |
| | THEIR PERSONAL USE? IF SO, A NOTE ADDRESSING THIS SHALL |
| | BE TO THE DRAWINGS, OTHERWISE AN ACCESSIBLE OUTLET |
| | POWERED FROM THE UNIT?S ELECTRICAL SERVICE SHALL BE |
| | INSTALLED INSIDE THE RESPECTIVE CLOSETS FOR THIS |
| | PURPOSE. |
| | 6. FOR COMPLIANCE W/THE 2010 FBC-ENERGY CONSERVATION |
| | CODE, THERE ARE LIGHTING REQUIREMENTS THAT ARE NOT |
| | ADDRESSED ON THE PLANS. SUCH ARE THE GASKET REQUIREMENT |
| | FOR RECESSED LIGHTING, THE EFFICIENT LIGHTING |
| | REQUIREMENT, ETC. |
| | |
| | PAGE E2.1.1 OVERALL GROUND FLOOR PLAN |
| | 1. IDENTIFY THE EXIT AND EXIT LIGHT IN THE GENERATOR |
| | ROOM |
| | 2. MISSING THE EXIT LIGHT IN THE DOMESTIC PUMP ROOM. |
| | 3. MISSING EXIT LIGHT FOR FIRE CONTROL ROOM |
| | 4. MISSING EXIT LIGHT FOR TRASH ROOM |
| | 5. MISSING EXIT LIGHT FOR VESTIBULE 116 B |
| | 6. MISSING EXIT FOR STAIR 5 & STAIR 1 |
| | 7. MISSING EXIT LIGHT OUTSIDE OF MAINTENANCE OFFICE |
| | 8. MISSING EXIT LIGHTS IN WORKROOM CLOUD AREA. |
| | |
| | THIS PAGE IS CO CLUTTERED THAT I MAY HAVE MISSED |
| | ADDITIONAL EXIT LIGHT REQUIREMENTS. PLEASE GO OVER THE |
| | DRAWING IN LAYERS TO SIMPLIFY EXIT LIGHT PLACEMENT. |
| | |
| | PAGE E2.2.1 OVERALL SECOND FLOOR PLAN |
| | 1. INSTALL AN EXIT LIGHT AS MARKED TO ANNOUNCE STAIR #4 |
| | FROM PARKING AREA. |
| | |
| | PAGE E2.3.1 OVERALL 3RD FLOOR & 5TH FLOOR PLAN |
| | 1. BIKE STORAGE ROOM 304 MISSING O/S SENSOR (EXIT IS |
| | POORLY IDENTIFIED) |
| | |
| | PAGE E2.4.1 OVERALL 4TH FLOOR PLAN |
| | 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S |
| | 404, 405, 407, 413 |
| | |
| | PAGE E2.5.1 OVERALL 5TH FLOOR PLAN |
| | 1. BIKE STG. ROOM 504 IS MISSING THE O/S |
| | |
| | PAGE E2.6.1 OVERALL 6TH FLOOR PLAN |
| | 1. THE FOLLOWING ROOMS ARE MISSING THE REQUIRED O/S: |
| | 603, 604, 605, 607, 608, 609, 612, & 613 |
| | 2. FCU-2 IS MISSING THE REQUIRED LIGHTING PER NEC |
| | 110.26(D) |
| | 3. POOL EQUIPMENT ROOM SHALL INCLUDE THE EQUIPMENT |
| | BEING INSTALLED TO VERIFY PROPER CLEARANCES. |
| | 4. NEC 680.22 (B) GFCI PROTECTIONS. OUTLETS SUPPLYING |
| | POOL PUMP MOTORS 15 OR 20 AMPERES, 125 VOLT OR 240 |
| | VOLT, SINGLE PHASE, WHETHER BY RECEPTACLE OR DIRECT |
| | CONNECTION, SHALL BE PROVIDED WITH GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. IF THE |
| | POOL HEATERS ARE TO BE STAND-ALONE, MEANING THAT THEY |
| | DO NOT DEPEND ON THE POOL CIRCULATING PUMPS FOR WATER |
| | CIRCULATION, THEY TOO SHALL BE GFCI PROTECTED. |
| | |
| | PAGE E2.7.1 OVERALL 7TH FLOOR PLAN |
| | 1. PER NOTES, POOL IS TO BE ON SEPARATE PERMIT THUS NO |
| | NOTES ADDRESSING POOL. |
| | |
| | PAGE E2.8.1 OVERALL TYPICAL 8TH ? 20TH FLOOR PLAN |
| | 1. RELOCATE EXITS SIGNS SO AS NOT TO CONFUSE |
| | PEDESTRIANS INTO WRONG DOORWAY. |
| | |
| | PAGE E3.1.1, UNITS 301/501 |
| | 1. 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE |
| | UNITS IN MULTIPLE LOCATIONS. |
| | 3. NEC 210.52 (A)(2) WALL SPACE. REQUIRES AN OUTLET ON |
| | EVERY WALL GREATER THAN 2?. SEE CLOUDS ON THE LIVING |
| | ROOM AND FOYER AND CORRECT ACCORDINGLY. |
| | 4. NEC 210.52 (C)(3) PENINSULAR COUNTERTOP SPACES. |
| | REQUIRES AT LEAST ONE RECEPTACLE AT EACH PENINSULA |
| | COUNTERTOP. THIS IS A COMMON ISSUE OCCURRING IN MOST |
| | ALL KITCHEN PENINSULAS, SEE CLOUDS. |
| | 5. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT |
| | THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT |
| | BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY |
| | UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR |
| | OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES |
| | PAGE. |
| | 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE |
| | |
| | PAGE E3.1.1, UNITS 302/502 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS OCCURS THROUGH THE |
| | UNITS IN MULTIPLE LOCATIONS |
| | 2. 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE |
| | THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| | THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE |
| | OUTLET IN THAT SPACE. |
| | 3. NEC 210.63 HVAC EQUIPMENT OUTLET. REQUIRES THAT |
| | THERE BE A SERVICE OUTLET WITHIN 25? OF THE EQUIPMENT |
| | BEING SERVICED. YOU WILL NOTICE THIS FOR MOST EVERY |
| | UNIT, SINCE THE HVAC EQUIPMENT IS IN THE CORRIDOR |
| | OUTSIDE THE UNIT. SEE MY NOTE 5 OF THE LEGEND & NOTES |
| | PAGE. |
| | 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING |
| | |
| | PAGE E3.1.1A UNITS 301/501 & 302/502 PANEL SCHEDULES |
| | 1. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 2. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 3. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.2.1, UNITS 303-503 & 304-504 |
| | 1. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE |
| | WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY |
| | FROM A RECEPTACLE OUTLET IN THAT SPACE. |
| | 2. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 3. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| | DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| | MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| | CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| | RELOCATE THE UNITS ACCORDINGLY |
| | 4. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 5. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 6. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.3.1, UNITS 305-505 |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREA IN |
| | KITCHEN |
| | 3. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE |
| | WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY |
| | FROM A RECEPTACLE OUTLET IN THAT SPACE. SEE CLOUDED |
| | AREA AND CORRECT ACCORDINGLY. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| | DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| | MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| | CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| | RELOCATE THE UNITS ACCORDINGLY |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.3.1, UNITS 306-506 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE CLOUDED AREAS |
| | LABELED IN FOYER, KITCHEN & BEDROOM |
| | 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE |
| | WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY |
| | FROM A RECEPTACLE OUTLET IN THAT SPACE. . SEE CLOUDED |
| | AREA AND CORRECT ACCORDINGLY. |
| | 3. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 5. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 6. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 7. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.4.1, UNIT 1 (TYP. 8 - 20 FLR.) |
| | 1. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN |
| | 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN THE PERIMETER OF THE BALCONY. |
| | 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.5.1, TYPICAL UNIT 2 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN |
| | EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE |
| | IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE |
| | FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE. |
| | 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.) |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN |
| | EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE |
| | IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE |
| | FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE. |
| | 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | 10. YOU MAY WANT TO CHECK YOUR CALCULATOR, SEE SMALL |
| | APPLIANCE LOAD ANALYSIS UNIT 3. |
| | |
| | PAGE E3.6.1, UNIT 3, (TYP. FOR 7 ? 19 FLR.) |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN |
| | EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE |
| | IS TO REMAIN FIXED AND THE PENINSULA AFFORDS A PLACE |
| | FOR AN OUTLET TO SOLVE THE DISTANCE FROM AN EDGE. |
| | 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. UNIT 3 OF PAGE E3.6.1 IS OF THE SAME SIZE, YET THE |
| | A/C LOAD ON ONE IS 5400VA AND THE OTHER HAS 8000VA |
| | 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD. |
| | |
| | PAGE E3.7.1, UNIT 4 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. THOUGH THERE IS AN |
| | EXCEPTION FOR THE SLIDING DOOR WE DON?T KNOW WHICH SIDE |
| | IS TO REMAIN FIXED |
| | 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 3. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | 9. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 10. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 11. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | 12. YOU MUST BE USING THE SAME CALCULATOR, SEE SMALL |
| | APPLIANCE LOAD ANALYSIS UNIT 4. |
| | |
| | PAGE E3.8.1, UNITS 5 |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE CLOUD MASTER BEDROOM |
| | 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | 10. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER |
| | EXTENDING INTO THE PATH OF THE DOOR |
| | 11. SEE CLOUD IN MASTER BATH COUNTER 805.05 |
| | |
| | PAGE E3.9.1, UNITS 6, 7, 8, 9, 10, 12 |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE FOYER |
| | 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E3.9.1A, TYPICAL UNIT 7, 9 |
| | 1. ACCORDING TO THE PAGE HEADING, THESE UNITS ARE |
| | SUPPOSED TO BE MIRRORED OF EACH OTHER, YET THERE ARE |
| | TWO PANEL SCHEDULES EACH WITH ITS RESPECTIVE LOAD |
| | ANALYSIS; BOTH OF WHICH ARE DIFFERENT. CORRECT THE LOAD |
| | ANALYSIS AND PANEL SCHEDULES OR REMOVE THE MIRROR |
| | REFERENCE. |
| | 2. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE FOYER |
| | 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP |
| | 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E3.10.1, TYPICAL UNIT 11 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE DEN & FOYER |
| | 2. NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 12 IN. OR WIDER. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE |
| | WALL LINE IS MORE THAN 24 IN. MEASURED HORIZONTALLY |
| | FROM A RECEPTACLE OUTLET IN THAT SPACE. |
| | 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 4. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 5. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | 10. THE SMOKE DETECTOR IN THE DEN IS NOT REQUIRED AS |
| | THIS IS NOT CONSIDERED A SLEEPING AREA; IF IT TO |
| | REMAIN, IT SHALL BE RELOCATED TO COMPLY WITH NFPA |
| | SECTION 29.8.3.4(6) WHICH REQUIRES THAT THE SMOKE |
| | DETECTOR NOT BE WITHIN 36? OF A BATHROOM WITH A SHOWER |
| | OR TUB. RELOCATE THIS UNIT ACCORDINGLY. |
| | |
| | PAGE E3.11.1, UNIT 11A, 7TH FLR |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. |
| | 2. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. |
| | 3. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 4. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 5. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 6. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 7. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 8. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | 9. JUST HAPPEN TO NOTICE THE BATHROOM COUNTER EXTENDING |
| | INTO THE PATH OF THE DOOR |
| | |
| | PAGE E3.12.1, UNIT 13 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM |
| | & BEDROOM 2. |
| | 2. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE FOYER. |
| | 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS. |
| | 4. NEC 210.520(D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH |
| | BASIN. SEE MASTER BATH. |
| | 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 8. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 9. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E3.13.1, UNIT 14 |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE MASTER BEDROOM. |
| | 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE FOYER. |
| | 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS. |
| | 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E3.14.1, UNIT 15 |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING ROOM, |
| | DINING ROOM & BEDROOM 2. |
| | 3. NEC 210.52 (A)(2) WALL SPACE. ANY SPACE 2 FT. OR |
| | MORE IN WIDTH. SEE DINING ROOM & WALL ADJACENT TO |
| | ELECTRIC PANEL |
| | 4. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS. |
| | 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. IN THE PROCESS OF MY ELECTRICAL PLAN REVIEW I TRIED |
| | TO VERIFY YOUR LOAD CALCULATIONS FOR COMPLIANCE AND NOT |
| | ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED TO |
| | LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION OF |
| | THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 8. I DON?T UNDERSTAND WHY YOU ARE COUNTING A LAUNDRY |
| | CIRCUIT AND LATER ADDING A WASHER LOAD |
| | 9. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E15.1, UNIT 15A, 7TH FLR |
| | 1. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THERE SHALL |
| | BE PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | 2. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. SEE LIVING & DINING |
| | ROOMS. |
| | 3. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| | PENINSULAR COUNTERTOP. SEE BOTH KITCHEN PENINSULAS. |
| | 4. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN |
| | 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN THE PERIMETER OF THE BALCONY. THOUGH I |
| | DON?T SEE THE TERRACE DELINEATION, ROOM 715.12 |
| | INDICATES A TERRACE. NO CLOUD DUE TO UNCERTAINTY OF |
| | TERRACE. |
| | 5. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. SEE MY NOTE 5 ON OF PAGE E1.0.0 LEGEND & |
| | NOTES |
| | 6. NEC 210.70(A)(3) STORAGE OR EQUIPMENT SPACES. AT |
| | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | THE CLOSET IN WHICH THE TV & TELEPHONE BOX/CABINET IS |
| | IN SHALL HAVE THE REQUIRED LIGHTING. SEE BEDROOM 2 |
| | CLOSET. |
| | 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 8. I REVIEWED YOUR LOAD CALCULATIONS FOR COMPLIANCE AND |
| | NOT ONLY DID I FIND THEM NOT TO BE CORRECT, BUT I TRIED |
| | TO LOCATE THE QUOTED CODE SECTIONS IN THE 2008 EDITION |
| | OF THE NEC AND WAS NOT ABLE TO FIND THEM |
| | 9. YOU ARE COUNTING A LAUNDRY CIRCUIT AND LATER ADDING |
| | A WASHER LOAD |
| | 10. IN DOING THE LOAD CALCS MYSELF I ARRIVED WITH A |
| | SMALLER LOAD USING THE STANDARD METHOD |
| | |
| | PAGE E4.1.1 PANEL SCHEDULES |
| | 1. INCLUDE THE RETAIL MAIN |
| | |
| | PAGE E5.1.1 POWER RISER |
| | 1. YOUR NOTES ON PAGE E5.2.1 DESCRIBE THESE CONDUCTORS |
| | AS HAVING THHN INSULATION. CORRECT THAT TO COMPLY WITH |
| | THE REQUIREMENTS OF NEC 300.5 B, STATING THAT THE |
| | INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE CONSIDERED |
| | A WET LOCATION AND THUS THWN IS REQUIRED. |
| | |
| | PAGE E6.3.1 ENLARGED ROOMS |
| | 1. NEC 110.26 A1 REQUIRES A MINIMUM OF 3? CLEAR WORKING |
| | SPACE IN FRONT OF ELECTRICAL EQUIPMENT; ACCORDING TO |
| | THE DRAWINGS THERE SEEMS TO BE ENCROACHMENT OF THIS |
| | SPACE IN THE ELECTRICAL ROOMS OF LEVELS 7, 9, 11, 14, |
| | 16, & 18. CHECK AND REVISE AS NECESSARY. |
| | |
| | PAGE E7.1.1 LIGHT FIXTURE SCHEDULES |
| | 1. I HAVE NOT SEEN ANYWHERE ON THE DRAWINGS A NOTE AS |
| | TO THE COMPLIANCE WITH THE 2010 FBC-ENERGY CONSERVATION |
| | CODE. |
| | |
| | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 |
| | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE |
| | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION. |
| | |
| | FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT: |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | PH: (561) 805-6743 |
| | EMAIL: [email protected] |
| | |
| | FIRE ALARM REVIEW UNDER SEPARATE COVER. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CONTACT ME. |