| 2015-05-17 14:08:14 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MAY 18 /2015 |
| | ACTION: DENIED |
| | |
| | 1) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN |
| | PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY |
| | REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| | PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE |
| | TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | |
| | 2) THE PERMIT APPLIED VALUE IS STATED AS $28,665,000.00 |
| | DOLLARS. THE CALCULATED VALUE IS $44,101,328.00 DOLLARS |
| | IN VALUE. USING THE FLOOR AREA SUMMARY FOUND ON 022 |
| | SP1.1. PLEASE PROVIDE THE SQUARE FOOTAGE PER FLOOR. |
| | PLEASE BREAK OUT MIXED USE OCCUPANCIES PER FLOOR. FOR |
| | THE PARKING GARAGE PLEASE PROVIDE AREA BY LEVEL. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED OVERLAY OF |
| | THE BUILDING TO VERIFY THE ACTUAL DISTANCE FROM |
| | PROPERTY LINES. 2010 FBC-B TABLE 602. |
| | 4) THE CURRENT SURVEY SUBMITTED INDICATES THIS PROPOSED |
| | STRUCTURE WILL BE LOCATED ON LOTS 11-15 OF BLOCK 10. A |
| | REPLAT WILL BE REQUIRED TO ELIMINATE THE BUILDING GOING |
| | PAST PROPERTY LINES. TABLE 602. |
| | |
| | 5) NO ENERGY REPORT AND CALCULATIONS WERE SUBMITTED. |
| | PLEASE PROVIDE CODE COMPLIANCE WITH THE 2010 FBC-ENERGY |
| | 103.2.1 CODE DEMONSTRATION FORMS, TABLE 103.2.1. |
| | |
| | 6) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 6A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 6B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | FORMS WERE SENT TO: : [email protected] AT |
| | 05/09/2015 02:09 PM. |
| | |
| | 6C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 6D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 6E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 6F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | |
| | 6G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 6H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 7) PAGE 024 LS-1.0, 032 A2.1.1 & 033 A2.1.2. |
| | |
| | 7A) THESE PLANS INDICATE 5 STAIRWELLS WITH STAIRS 4 & 5 |
| | HAVING THE EXIT DISCHARGE DIRECTLY AT THE EXTERIOR OF |
| | THE BUILDING. STAIR 1 EXITS THE VERTICAL ENCLOSURE |
| | TRAVEL THROUGH THE ELEVATOR LOBBY, MAIN LOBBY AND |
| | GALLERY BEFORE THE EXIT DISCHARGE IS ARRIVED AT. IN THE |
| | ELEVATOR LOBBY THERE ARE (2) COLUMNS AND SOME WALL TYPE |
| | THAT WOULD BLOCK THE VIEW OF THE MAIN ENTRANCE, MORE |
| | INFORMATION IS REQUIRED HOW THIS WILL QUALIFY UNDER THE |
| | EXCEPTIONS FOUND IN SECTION FBC-B 1027.1 IT APPEARS |
| | EXCEPTION 1 WOULD BE TAKEN? |
| | |
| | 7B) THE OTHER STAIRWELL # 3 IT APPEARS IS ALSO TAKING |
| | THE SAME EXCEPTION FOUND IN 2010 FBC-B 1027.1 EXCEPTION |
| | # 1. THE 2007 FBC CODE COMMENTARY DOES IN PRINCIPLE |
| | AGREE, THERE IS LANGUAGE DOES LEAVE ROOM FOR QUESTION. |
| | THIS DOES NOT MEAN THE EXTERIOR EXIT DOOR MUST BE |
| | DIRECTLY IN FRONT OF THE DOOR AT THE BOTTOM OF THE |
| | STAIRWAY, BUT THE INTENT IS THAT IT SHOULD BE WITHIN |
| | THE GENERAL RANGE OF VISION. IT SHOULD NOT BE REQUIRED |
| | THAT A PERSON MUST TURN COMPLETELY AROUND OR GO AROUND |
| | A CORNER TO BE ABLE TO SEE THE WAY OUT. |
| | |
| | 7C) STAIRWELL # 2 ROOM 139 IS SHOWN WITH A 2 HR. |
| | ENCLOSURE DOOR 139 1 ? HOUR OPENING PROTECTIVE. THE |
| | EXTENSION OF THE EXIT IS LABELED AS AN EXIT ACCESS |
| | CORRIDOR # 115. PLEASE NOTE THIS IS AN EXIT PASSAGE WAY |
| | AND NEEDS TO COMPLY WITH SECTION FBC-B 1023.6 |
| | PENETRATIONS. THE MECHANICAL AND ELECTRICAL PLANS |
| | INDICATE AN INTAKE AIR LOUVER AN FAN WITH 2160 CFM TO |
| | PRESSURIZE THE EXIT PASSAGEWAY. NOTE NO ELECTRICAL RACE |
| | WAYS, CONDUITS, ETC. FROM THE FPL VAULT OR FROM THE |
| | SWITCHGEAR/ ELECTRICAL ROOM RUN THROUGH THIS EXIT |
| | PASSAGEWAY. |
| | |
| | 7D) PLEASE NOTE THE EXIT PASSAGEWAY 115 THE TOP AND |
| | BOTTOM SLOPED AREAS MEET THE DEFINITION OF GRADE WITH A |
| | SLOPE OF 1:20 THE MIDDLE SECTION FROM LANDING MARKED AS |
| | 12.75 FT. TO LANDING 12.08 FT. IS A DIFFERENCE OF 8 |
| | INCHES X 20= 160 INCHES (13.3 FT. RAMP FBC-B 1010.2 |
| | SLOPE) OF RUN REQUIRED NOT TO BE CONSIDERED A RAMP. |
| | THIS SECTION WILL NEED TO COMPLY WITH 2010 FBC-B 1010.8 |
| | HANDRAILS. |
| | |
| | 7E) THE PLANS INDICATE A SERIES OF LOUVERS AND WALL |
| | OPENINGS, THE OPENINGS DO NOT SHOW ANY PROTECTION NOR |
| | DOES THE LOUVERS WITH THE EXCEPTION OF LOUVER 17 SEE |
| | SHEET A7.4. THE FBC-B TABLE 705.8 BASES THE AMOUNT OF |
| | OPENINGS BASED ON THE SEPARATION DISTANCE. WHEN FACING |
| | PUBLIC RIGHT OF WAYS STREETS OR ALLIES AN ASSUMED |
| | PROPERTY LINE IS TAKEN FROM THE CENTER OF THE STREET OR |
| | ALLEY WAY OR IN THIS CASE 7?-0? FROM THE |
| | PROPERTY LINE, ALSO SEE FOOTNOTE (A) THE VALUES |
| | INDICATED ARE THE PERCENTAGE OF THE AREA OF THE |
| | EXTERIOR WALL, PER STORY. |
| | |
| | 7F) TRASH TERMINATION ROOM # 117 HAS (2) DOORS A SWING |
| | DOOR LISTED AS 117 WHILE THE OVERHEAD DOOR DOES NOT |
| | HAVE A IDENTIFICATION TAG, NOR DOOR RATING AS REQUIRED |
| | BY 2010 FBC-B 70813.4. |
| | |
| | 7G) THE DOOR 101 SEPARATING THE S2 STORAGE OCCUPANCY |
| | FROM THE BUSINESS OCCUPANCY IS MISSING THE DOOR RATING |
| | ON THE DOOR SCHEDULE, PAGE 126 A.7.1.1. 2010 FBC-B |
| | TABLE 715.4. |
| | |
| | 7H) THIS NOTE IS COMMON FOR ALL FLOORS. IN REVIEWING |
| | THE VARIOUS DOORS IN EXIT ENCLOSURES FOR THERE FIRE |
| | RATINGS IN THE DOOR SCHEDULE LISTED ON PAGE 126 A7.1.1 |
| | THERE IS A NOTE # 1 FOR HARDWARE SETS REFER TO |
| | SPECIFICATIONS. PLEASE NOTE SPECIFICATIONS ARE |
| | SOMETHING WE NORMALLY DO NOT REVIEW SINCE THEY CAN BE |
| | SEVERAL HUNDRED PAGES IN LENGTH. PLEASE PROVIDE A |
| | HARDWARE SCHEDULE THAT RELATES TO THE DOOR SCHEDULE SO |
| | CODE COMPLIANCE CAN BE REVIEWED. NORMALLY |
| | SPECIFICATIONS ARE STAMPED VOID NOT REVIEWED. |
| | 7I) PLEASE PROVIDE THE 1ST FLOOR SQ. FOOTAGE VERSES THE |
| | OWNERS STORAGE LOCKER AREA TO SEE IF THIS AREA |
| | QUALIFIES AS AN MIXED USE OCCUPANCY REQUIRING |
| | SEPARATION. 2010 FBC-B 508.2.1. |
| | 7J) HORIZONTAL TRELLIS FOUND ON THE SOUTH & WEST SIDES |
| | OF THE BUILDING SEE SECTION 6,8 & 9 PAGE A7.5.4. PLEASE |
| | SHOW WIND DESIGN AND ANCHORING DETAILS. FBC-B |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7K) NOTE!!! THE FPL VAULT TO BE BUILT TO THE AGREEMENT |
| | BETWEEN FPL AND PROPERTY OWNER. |
| | 7L) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F] |
| | 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS. OUTSIDE OPENINGS |
| | ACCESSIBLE TO THE FIRE DEPARTMENT AND THAT OPEN |
| | DIRECTLY ON A HOISTWAY OR SHAFTWAY COMMUNICATING |
| | BETWEEN TWO OR MORE FLOORS IN A BUILDING SHALL BE |
| | PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED LETTERS |
| | AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. |
| | SUCH WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY |
| | DISCERNIBLE FROM THE OUTSIDE OF THE BUILDING. |
| | 7M) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: F |
| | 914.1.2 INTERIOR ACCESS TO SHAFTWAYS. DOOR OR WINDOW |
| | OPENINGS TO A HOISTWAY OR SHAFTWAY FROM THE INTERIOR OF |
| | THE BUILDING SHALL BE PLAINLY MARKED WITH THE WORD |
| | ?SHAFTWAY? IN RED LETTERS AT LEAST 6 INCHES (152 MM) |
| | HIGH ON A WHITE BACKGROUND. SUCH WARNING SIGNS SHALL BE |
| | PLACED SO AS TO BE READILY DISCERNIBLE. |
| | 7N) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| | 914.2 EQUIPMENT ROOM IDENTIFICATION. FIRE PROTECTION |
| | EQUIPMENT SHALL BE IDENTIFIED IN AN APPROVED MANNER. |
| | ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, |
| | SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, |
| | SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED FOR |
| | THE USE OF THE FIRE DEPARTMENT. APPROVED SIGNS REQUIRED |
| | TO IDENTIFY FIRE PROTECTION EQUIPMENT AND EQUIPMENT |
| | LOCATION SHALL BE CONSTRUCTED OF DURABLE MATERIALS, |
| | PERMANENTLY INSTALLED AND READILY VISIBLE. |
| | 7O) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B: [F] |
| | 915.1 GENERAL. [F] 915.1 GENERAL. |
| | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 7P) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B 916.1 |
| | CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR |
| | AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT |
| | FOR NEW CONSTRUCTION IS ISSUED AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR |
| | ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF |
| | COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE |
| | ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR |
| | SLEEPING PURPOSES IN THE NEW BUILDING OR ADDITION, OR |
| | AT SUCH OTHER LOCATIONS AS REQUIRED BY THIS CODE. |
| | |
| | 8) 2ND FLOOR, PAGE 025 LS-2-0, 035 A2-2-1,& A-2-2-2. |
| | 8A) THE HANDICAPPED SPACE # 58 DOES NOT HAVE A 5?-0? |
| | CLEAR ACCESS AISLE NEXT TO IT, THERE IS A COLUMN IN THE |
| | WAY AT GRID LINE C.6 AND 1.5. NOTE THE COLUMN IS 3FT 3 |
| | INCHES FROM THE ACCESSIBLE PARKING SPACE, EVEN THOUGH |
| | THE AISLE IS WIDER IF THE COLUMN IS AT A POINT WHERE |
| | THE DOOR CANNOT BE OPENED NOR A VANS ACCESSIBLE |
| | PLATFORM CANNOT BE LOWERED. |
| | 8B) THERE IS (2) AREAS NOT CLEAR AS TO WHERE THE |
| | CEILING IS LOCATED OR IF THE BLOCK WALL GOES ALL THE |
| | WAY TO THE 3RD FLOOR. SEE FPL TRANSFORMER VAULT AND |
| | SWITCHGEAR/ ELECTRIC ROOM. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 9) PAGE 026 LS-3.0, PAGE 038 A2.3.1 & PAGE 039 A2.3.2: |
| | 9A) DOORS 307.02 & 307.03 BOTH DOORS ARE CONSIDERED |
| | COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE |
| | UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON |
| | THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING |
| | REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION |
| | 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF |
| | AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS |
| | OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN |
| | INDIVIDUAL DWELLING UNITS. |
| | (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| | AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| | THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| | 9B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS |
| | FOUND ON: |
| | PAGE 078 A6.1.2 UNIT 301 & 302 |
| | PAGE 080 A6.2.2 UNIT 303 & 304 |
| | PAGE 083 A6.3.2 UNIT 305 & 306 |
| | PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR |
| | INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR |
| | THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS |
| | WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT |
| | SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE |
| | 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A |
| | GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS |
| | WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ? |
| | HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT |
| | GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION |
| | CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB. |
| | 10) PAGE 027 LS 4.0, PAGE 041 A2.4.1 & PAGE 042 A2.4.2: |
| | NOTE: COMMENTS FOR THE 4TH FLOOR WILL ALSO STAND FOR |
| | THE 6TH FLOOR. |
| | |
| | 10A) THE COMMON CMU WALL BETWEEN THE PARKING GARAGE AND |
| | OPEN AIR 3RD STORY DWELLING UNITS (CLEARSTORY) IS A 2 |
| | HOUR FIRE RATED WALL. THE STRUCTURAL SHEETS SHOW |
| | DETAILS OF THIS WALL PAGE 171 S2.40 SHOWS A DETAIL #7 |
| | FOUND ON S5-10. THIS DETAIL SHOW A REINFORCED CONCRETE |
| | POURED 8 INCH WALL TO COMPLY WITH FBC-B 1607.7.3 |
| | VEHICLE BARRIER SYSTEMS. THERE ARE (2) POINTS OF |
| | LOADING TO CONSIDER, PLEASE PROVIDE HOW THE 2ND IS MET: |
| | THE SECOND LOADING CONDITION SHALL APPLY THE LOAD AT 2 |
| | FEET, 3 INCHES (686 MM) ABOVE THE FLOOR OR RAMP |
| | SURFACE. THE MORE SEVERE LOAD CONDITION SHALL GOVERN |
| | THE DESIGN OF THE BARRIER. |
| | 10B) THE 2ND COMMENT DEALS WITH AN ACCESSIBLE PARKING |
| | SPACE AND ACCESS AISLE NEXT TO STAIR # 3. THE FAIR |
| | HOUSING REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND |
| | COMMON USE AREAS. ANSI 117.1 GENERAL SITE AND BUILDING |
| | ELEMENTS. SECTION 503.3 ACCESS AISLES. WIDTH 503.3.1 60 |
| | INCHES/ LENGTH 503.3.2 20 FT. LONG MINIMUM. |
| | 11) PAGE 028 LS 5.0, PAGE 044 A2.5.1 & PAGE 045 A2.5.2: |
| | 11A) DOORS 507.02 & 507.03 BOTH DOORS ARE CONSIDERED |
| | COMMON AREA DOORS SINCE THEY ARE NOT ENTRY DOORS TO THE |
| | UNIT. THE 2 DOORS DO NOT HAVE THE 18 INCHES REQUIRED ON |
| | THE LATCH SIDE OF THE DOOR, PER FAIR HOUSING |
| | REQUIREMENT 3. USABLE DOORS. GUIDELINE SECTION |
| | 100.205(C)(2) WOULD APPLY TO DOORS THAT ARE A PART OF |
| | AN ACCESSIBLE ROUTE IN THE PUBLIC AND COMMON USE AREAS |
| | OF MULTIFAMILY DWELLINGS AND TO DOORS INTO AND WITHIN |
| | INDIVIDUAL DWELLING UNITS. |
| | (1) ON ACCESSIBLE ROUTES IN PUBLIC AND COMMON USE AREAS |
| | AND FOR PRIMARY ENTRY DOORS TO COVERED UNITS, DOORS |
| | THAT COMPLY WITH ANSI 4.13 WOULD MEET THIS REQUIREMENT. |
| | |
| | 11B)NOTE THIS WILL BE A COMMON STATEMENT FOR ALL UNITS |
| | FOUND ON: |
| | PAGE 078 A6.1.2 UNIT 501 & 502 |
| | PAGE 080 A6.2.2 UNIT5303 & 504 |
| | PAGE 083 A6.3.2 UNIT 505 & 506 |
| | PLEASE NOTE THE TENANT SEPARATION WALLS FOR THIS FLOOR |
| | INDICATE A 1 HOUR FIRE RATING BUT THE DOOR SCHEDULE FOR |
| | THE TYPICAL DWELLING UNIT DOORS SHOWS THE ENTRY DOOR AS |
| | WELL AS THE A/C CLOSET DOOR THAT IS WITHIN THE TENANT |
| | SEPARATION WALL BOTH SHOW 20 MIN. DOORS. FBC-B TABLE |
| | 715.4 DOES ALLOW FOR 20 MIN. DOORS INTO CORRIDORS FOR A |
| | GENERAL RULE. SECTION 709.3 FIRE RESISTANCE RATINGS AS |
| | WELL IN EXCEPTION # 1 ALLOWS FOR CORRIDOR WALLS TO BE ? |
| | HR. RATED. EXCEPTION # 2 FOR DWELLING UNITS DOES NOT |
| | GIVE THE REDUCTION FOR TYPE I BUILDINGS, THE REDUCTION |
| | CAN ONLY TAKE PLACE IN TYPE IIB, IIIB AND VB. |
| | |
| | 11C) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL |
| | FLOORS,(FLOOR SLABS ARE 8 INCH POST TENSION SLABS) THE |
| | 3RD -16TH STORY. PLEASE PROVIDE COMPLIANCE WITH BLDG |
| | TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | |
| | 11C)(1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 11C)(1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 11C)(1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS |
| | NONCOMBUSTIBLE MATERIALS. |
| | |
| | 12) PAGE 030 LS 7.0, PAGE 050 A2.7.1 & PAGE 051 A2.7.2: |
| | 12A) COMMON ROOM 701.01 APPROXIMATELY 1286 SQ. FT./ 15= |
| | 85 OCCUPANTS, THIS ROOM WILL REQUIRE 2 EXITS. NOTE ONE |
| | EXIT IS THROUGH THE ELEVATOR LOBBY (700) TO STAIR 701. |
| | THE LIFE SAFETY SHEET DOES NOT SHOW EXITING FOR THIS |
| | ROOM. 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE |
| | MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER |
| | PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701 |
| | CANNOT BE USED FOR THIS FLOOR AS DEPICTED! |
| | 12B) THE POOL DECK AND POOL SURFACE AREA TOTAL OCCUPANT |
| | LOAD EQUAL A TOTAL OF 121 OCCUPANTS. PLEASE PROVIDE THE |
| | (2) MEANS OF EGRESS WITHOUT GOING THROUGH THE ELEVATOR |
| | LOBBY. IN REALITY STAIRWELL 701 CANNOT BE USED FOR THIS |
| | FLOOR AS DEPICTED! |
| | 12C) EXIT ROUTE # 07 WEST TRAVELS THROUGH THE ELEVATOR |
| | LOBBY. . 708.14.1 ELEVATOR LOBBIES SHALL HAVE AT LEAST |
| | ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER |
| | PROVISIONS WITHIN THIS CODE. IN REALITY STAIRWELL 701 |
| | CANNOT BE USED FOR THIS FLOOR AS DEPICTED! |
| | 12D) DOOR 706F DOES NOT COMPLY WITH THE FAIR HOUSING |
| | GUIDE LINES REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC |
| | AND COMMON USE AREAS. ANSI A117.1 TABLE 404.2.4.1 |
| | MANEUVERING CLEARANCES FOR MANUAL SWING DOORS. |
| | 12E) NOTE THIS POOL DECK AND POOL ARE COVERED UNDER THE |
| | FAIR HOUSING ACT, TO DATE THE GUIDELINES ONLY REQUIRES |
| | ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, NOT AN |
| | ACCESSIBLE ROUTE(RAMP OR LIFT) DOWN INTO THE WATER INTO |
| | THE POOL. ON THE OTHER HAND IF THE ASSOCIATION ELECTS |
| | TO ALLOW THE COMMUNITY ROOM, POOL, AND OR POOL DECK TO |
| | BE RENTED OUT FOR PARTIES THAT THE PUBLIC COULD USE, |
| | THEN THIS AREA WOULD BE REQUIRED TO MEET FLORIDA |
| | ACCESSIBILITY SECTION 1009 OF THE ACCESSIBILITY CODE |
| | POOL LIFTS. |
| | 12F) THIS NOTE WILL BE A COMMON NOTE FOR FLOORS 7-20TH |
| | FLOORS. THE DOOR SCHEDULE FOUND ON PAGE 126 A.7.1.1 |
| | (DOOR SCHEDULE) IN THE REMARKS COLUMN THERE ARE VARIOUS |
| | DOORS IN THE CORRIDOR THAT STATE THAT A FIRE DAMPER IS |
| | TO BE INSTALLED IN THE LOUVERED DOOR. PLEASE SHOW |
| | COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 715.4.6 LABELED PROTECTIVE ASSEMBLIES. FIRE |
| | DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY. |
| | THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL BE |
| | PERMANENTLY AFFIXED TO THE DOOR OR FRAME INSTALLED |
| | WITHIN THE LOUVERED DOOR. |
| | |
| | 716.5.2 FIRE BARRIERS. DUCTS AND AIR TRANSFER OPENINGS |
| | OF FIRE BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE |
| | DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| | |
| | 12G) PAGE 023 LS-0.1 LIST THE REQUIRED FIRE SEPARATION |
| | DISTANCE FOR THE REQUIRED HOURLY RATING AND AMOUNT OF |
| | ALLOWABLE OPENINGS. SHEET A2-7.2 THE EAST PROPERTY LINE |
| | WALL IS APPROX. 13 FEET AWAY FROM THE OPENINGS, FBC-B |
| | TABLE 705.8 ALLOWS 45% UNPROTECTED SPRINKLERED, PLEASE |
| | PROVIDE THE PERCENTAGE OF ALLOWABLE OPENING TAKEN PER |
| | FLOOR LEVEL. |
| | 13) PAGE 031 LS 8.0, PAGE 053 A2.8.1 & PAGE 054 A2.8.2. |
| | 8TH-20TH FLOORS COMMON TO ALL FLOORS. |
| | 13A) THIS PAGE SHOWS SLIDING GLASS DOOR (SGD 6) IN UNIT |
| | 815 BEDROOM # 02, THE DOOR SCHEDULE (129 A7.3.1) |
| | INDICATES THIS SLIDING GLASS DOOR IS A 6FT. 4 IN. IS |
| | THIS A ROUGH OPENING SIZE OR OUTSIDE DOOR JAMB OPENING, |
| | NOT CLEAR. IN THE FAIR HOUSING GUIDE THE EXTERIOR |
| | SLIDING GLASS DOORS WILL NEED TO MEET REQUIREMENT # 4 |
| | (2) |
| | A MINIMUM CLEAR WIDTH OF 32 INCHES IS PROVIDED. |
| | |
| | 13B) FOR ALL SLIDING GLASS DOORS THE HARDWARE WILL ALSO |
| | NEED TO MEET THE ANSI 117.1 STANDARD 404.2.7. |
| | |
| | 14) PAGE 056 A.2.9.1: |
| | |
| | 14A) ROOF NOTE # 3 : |
| | THE NO LESS THAN R-10 IN ANY LOCATION LIKE ROOF DRAINS |
| | STILL HAS TO HAVE A MINIMUM OF R-19 INSULATION. SEE THE |
| | 2010 FBC-ENERGY CODE 506.2.1 UNDER TOTAL BUILDING |
| | PERFORMANCE METHOD. |
| | SEE BOAF INFORMAL INTERPRETATION # 5438 |
| | |
| | DATE: TUE NOV 13 2007 |
| | REPORT #: 5438 |
| | CODE: BUILDING |
| | SECTION: 404.1.A |
| | QUESTION: |
| | IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL |
| | HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO |
| | MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19 |
| | AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE |
| | SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE |
| | R-19, NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB |
| | ACCORDINGLY. THANK YOU |
| | ANSWER: A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, |
| | A MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE |
| | MINIMUM R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING |
| | PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF |
| | THE VALUE. |
| | COMMENTARY: THIS QUESTION ACTUALLY REFERS TO SECTION |
| | 13-404.1 (A) PRESCRIPTIVE REQUIREMENTS SPECIFIC TO |
| | METHOD A. THIS SECTION MANDATES COMPLIANCE WITH FLA/COM |
| | METHOD A, HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF |
| | AN R-19 FOR MULTIFAMILY RESIDENTIAL ROOF/CEILING |
| | ASSEMBLY. AS SPACE PERMITS, MAY RELATE TO THE AREA OF |
| | THE EAVES WHERE THE R- 19 INSULATION WOULD HAVE TO BE |
| | COMPRESSED TO FIT IN THE SPACE AVAILABLE. HOWEVER, THE |
| | PETITIONER ALLUDES TO THE ROOFER INSTALLING THE |
| | INSULATION. THERE ARE NO SPACE CONSTRAINTS FOR |
| | INSULATION APPLIED TO A ROOF DECK; IT SHOULD BE R-19 |
| | MINIMUM. IF THE BUILT-UP ROOF IS SLOPING TO A DRAIN IN |
| | A MANNER WHERE SOME PARTS OF THE ROOF HAVE MORE THAN |
| | R-19 AND SOME HAVE LESS, THEN THE RESIDENT WHOSE |
| | APARTMENT/CONDO IS UNDER THE ROOF SECTION WITH LESS |
| | THAN R- 19 WOULD BE PENALIZED WITH HIGHER HEAT LOADS |
| | AND HIGHER ENERGY COSTS THAN THEIR NEIGHBOR. |
| | |
| | 14B) ROOF NOTE # 6 REFERENCES THE USE OF CHEN-CURB OR |
| | EQUAL FOR PIPE OR TUBE ROOF PENETRATIONS. THE PRODUCT |
| | SPECIFIED HAS TO BE SPECIFIC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 14C) ROOF DRAINAGE CALCULATIONS DO NOT PROVIDE THE RATE |
| | OF RAINFALL PER HR. THE CHARTS WERE DESIGN FOR. |
| | P] 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO |
| | DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF |
| | DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| | |
| | 14D) THE QUESTION IS THE TOP OF ROOF DRAINS IS SHOWN AS |
| | MINUS INCHES FROM THE TOP OF ROOF, FOR EXAMPLE BOTH |
| | AREAS OF THE ROOF DESIGNATED AS N & P BOTH SHOW A -7 |
| | INCHES T.O.D. OR -7 INCHES FROM THE TOP OF THE HIGHEST |
| | ROOF DECK WHERE THE DECK ADJOINS TO THE PARAPET WALL. |
| | DETAIL 5/ A7.5.1 SHOWS THE EMERGENCY OVERFLOW SET AN |
| | ADDITIONAL 2 INCHES ABOVE THE 7 INCHES TOP OF DRAIN OR |
| | 9 INCHES OF DEPTH OF WATER BEFORE WATER CAN START TO |
| | OVERFLOW THE EMERGENCY ROOF SCUPPERS. IN ROOF ZONE P, |
| | THIS IS APPROXIMATELY 42,553 LBS. OF WATER WEIGHT. |
| | |
| | FBC-B 1503.4.2.1 WHEN LOOKING AT THIS SECTION THE |
| | INTENT IS WHEN THE ROOF IS SLOPED TO A SCUPPER THE, THE |
| | SCUPPER SHALL BE PLACED LEVEL (1503.4.2) TO THE ROOF |
| | DECK. THE EMERGENCY OVERFLOW SCUPPERS ARE TO BE PLACED |
| | 2 -4 INCHES ABOVE THE SCUPPER. THIS IS A COMMON MISTAKE |
| | WHEN APPLYING 1503.4.1 SECONDARY DRAINAGE REQUIRED. IF |
| | THE ROOF DRAINS ARE TO BE THE PRIMARY DRAIN THEN |
| | SHOULDN?T THE EMERGENCY OVERFLOW SCUPPERS BE PLACED 2 |
| | TO 4 INCHES ABOVE THE DRAIN? IF USING A SECONDARY ROOF |
| | DRAIN THAT IS HOW IT WOULD BE SET UP 2 TO 4 INCHES |
| | ABOVE THE ROOF DRAIN. |
| | |
| | 14E) THE PLANS INDICATE THE USE OF PRE-ENGINEERED A/C |
| | STANDS. WHEN FIGURING THE REQUIRED CLEARANCES IN HEIGHT |
| | REQUIRED BY TABLE FBC-B 1509.7, THE CLEARANCE IS FROM |
| | THE FINISHED ROOF HEIGHT, ABOVE THE LIGHTWEIGHT |
| | CONCRETE ROOF. |
| | |
| | 15) THIS IS MORE OF A CONCERN FOR THE FIRE DEPARTMENT |
| | AS TO HOW THE FIRE DEPARTMENT WILL BE ABLE TO GAIN |
| | ENTRY WHEN THE TILT GATES TO THE GARAGE ARE DOWN? WILL |
| | THE GARAGE TILT GATES BE ON EMERGENCY POWER CIRCUITRY? |
| | IN THE EVENT OF GATE FAILING TO OPEN HOW WILL EGRESS TO |
| | MAINTAINED ? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED? |
| | |
| | 16) PAGES 126 A7-1-1, 127 A7-2-1, 129 A7-3-1, 130 |
| | A7-3-2, 131 A7-3-3 & 132 A7-4-1. ALL OF THESE SHEETS |
| | DEAL WITH THE EXTERIOR OF THE BUILDING AND WITH |
| | COMPONENTS & CLADDING. |
| | |
| | 16A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 16B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC |
| | |
| | 16C) IF EITHER THE CONTRACTOR OR DESIGNER OF RECORD |
| | WISH TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT |
| | ISSUANCE PLEASE INFORM SO IN WRITING. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION. 107.3.4.3 |
| | CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE |
| | PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL |
| | BE CONSIDERED EQUIVALENT TO SEALED PLANS AND |
| | SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471, |
| | FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY |
| | LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR |
| | PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE |
| | WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE |
| | METHODOLOGIES APPROVED BY THE FLORIDA BUILDING |
| | COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL |
| | ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION |
| | BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS |
| | SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR |
| | WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL |
| | GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR |
| | REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS |
| | 471,481 OR 489, FLORIDA STATUTES. |
| | |
| | 17) PAGES 163 S1.13 AND 164 S1.14. NOTE # 1 ON THESE |
| | SHEETS INDICATE THE PRESSURES WERE CALCULATED USING THE |
| | CALCULATED BY CODE ANALYTICAL METHODS. THIS TERM |
| | ANALYTICAL METHOD DOES NOT SHOW UP IN THE CODE WHEN A |
| | WORD SEARCH IS COMPLETED. IT WOULD APPEAR THAT A WIND |
| | TUNNEL TEST WAS COMPLETED AS ALLOWED BY FBC-B 1609.1.1 |
| | EXCEPTION 6. WIND TUNNEL TEST ARE TO BE IN ACCORDANCE |
| | WITH CHAPTER 31 OF ASCE 7. PLEASE PROVIDE THE SIGNED |
| | AND SEALED WIND TUNNEL TEST OR PROVIDE HOW THESE |
| | PRESSURES WERE DERIVED. |
| | |
| | 18) PAGE 165 THE FOUNDATION PLAN SHOWS ALL PILE CAP |
| | DIRECTLY ON THE PROPERTY LINE. A REVISION MAY BE |
| | REQUIRED. THE SOILS REPORT INDICATES THAT THIS SITE HAS |
| | LOOSE SOILS AND BECAUSE OF THE CLOSENESS OF OTHER |
| | BUILDINGS AROUND THE SITE, VIBROFLOTATION WAS NOT |
| | RECOMMENDED AND AUGERED CAST PILES CAST IN PLACE SHOULD |
| | BE USED TO SUPPORT THE STRUCTURE. THE SOILS REPORT WENT |
| | IN DEPTH OF HOW THE UTILITIES IN THE ALLEY WOULD NEED |
| | TO BE SUPPORTED AND HOW TO COMPLETE THIS TASK. |
| | |
| | LAST WEEK (MAY 12/2015) IN A MEETING WITH MATT STILL |
| | THE PROJECT MANAGER , MATT SPOKE ABOUT THE POSSIBLE USE |
| | OF SHEET PILING AROUND THE PERIMETER OF THE PROJECT. |
| | THIS WILL HAVE THE SAME EFFECT AS VIBROFLOTATION AS TO |
| | DAMAGE TO STRUCTURES IN THE VICINITY OF THE PROJECT. A |
| | RESOLUTION ON THIS MATTER WILL NEED TO TAKE PLACE IF |
| | SHEET PILE ARE GOING TO BE INSTALLED AROUND THE |
| | PERIMETER, THIS WILL AFFECT THE PLACEMENT OF THE PILE |
| | AND PILE CAPS. |
| | |
| | 19) PAGE A7.5.3 ; |
| | 19A) NOTE: THE POOL TRELLIS STRUCTURE (PERGOLA) THIS |
| | DETAIL INDICATES IT IS GOING TO BE DESIGNED BY A |
| | SPECIALTY ENGINEER. BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT, THE PLANS WILL NEED TO BE REVIEWED BY THE |
| | ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED |
| | ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| | DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 19B) THE POOL TRELLIS STRUCTURE (PERGOLA) THIS |
| | STRUCTURE INDICATES THE USE OF A PLEXIGLASS RAIN GUARD. |
| | PLEASE PROVIDE HOW THE PLEXIGLASS RAIN GUARD WILL MEET |
| | THE FIRE RESISTANCE RATINGS REQUIRED BY FBC-B TABLE 601 |
| | AND FBC-B TABLE 1505.1.ALSO SEE FBC-B 2610 2610.4. WILL |
| | THERE BE FIRE SPRINKLERS BENEATH THIS STRUCTURE. |
| | |
| | 20) PAGE 136 A7.5.4. |
| | 20A) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC |
| | WRAPPED WILL REQUIRE WIND DESIGN CRITERIA SEE OPTIONS |
| | FOUND UNDER FBC-B 3105.4 . ALSO: FL 61G-15-30.006 (3) |
| | THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 20B) DETAIL # 5 RIGID ALUMINUM CANOPY WITH FABRIC |
| | WRAPPED WILL NEED TO MEET THE REQUIREMENTS OF 3105.3.1 |
| | FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL |
| | MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA |
| | 701. |
| | |
| | 21) PAGE 137 A7.5.5 DETAIL # 10 THE BALCONY EDGE |
| | ALUMINUM RAILING DOES NOT HAVE THE DESIGN CRITERIA THAT |
| | WILL BE REQUIRED TO MANUFACTURER, THE BALCONY RAIL WILL |
| | NEED TO MEET THE FOLLOWING : |
| | FBC-B 1607.7.1.1 CONCENTRATED LOAD & . 1607.7.1.2 |
| | COMPONENTS. |
| | |
| | 22) PAGE 139 A9.1.1 STAIRWELL NUMBER 1 DOES NOT SHOW |
| | THE STANDPIPE IN THE STAIRWELL NOR ARE THERE ANY NOTES |
| | ONE IS REQUIRED. FBC-B 905.3.1. THIS COMMENT STAND FOR |
| | ALL STAIRWELLS. PLEASE NOTE THE ONLY PENETRATIONS |
| | ALLOWED IN THE STAIRWELL ARE TOUGHS THAT COMPLY WITH: |
| | |
| | FBC-B 1022.4 PENETRATIONS. PENETRATIONS INTO AND |
| | OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| | EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK |
| | NECESSARY FOR INDEPENDENT VENTILATION OR |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 23) PAGE 153 A11.2: |
| | 23A) DETAIL # 1 THE TRASH TERMINATION ROOM, SHOW A |
| | STAINLESS STEEL ROLLING FIRE DOOR WITH 165 DEGREE |
| | FUSIBLE LINK, THE PLANS DO NOT INDICATE WHAT THE FIRE |
| | DOOR IS RATED TOO? FBC-B TABLE 715.4. |
| | |
| | 23B) THE THROUGH THE FLOOR FIRE PROOFING DETAIL |
| | INDICATE THE USE OF MINERAL WOOL INSULATION PLEASE |
| | PROVIDE A LISTED ASSEMBLY FOR A 2?-0? DIAMETER STEEL |
| | TRASH CHUTE, NOT FOUND ON THE UL ASSEMBLY SHEET. FBC-B |
| | 713.4.1.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| | HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| | 713.4.1.1.1 OR 713.4.1.1.2. |
| | |
| | 23C) THROUGH PENETRATION OF FLOOR SLAB FOR TUB DRAIN IF |
| | TRAP IS WITHIN THE FLOOR ASSEMBLY IS NOT PROVIDED ON |
| | THE UL ASSEMBLY SHEETS NOR P5.1.2. THROUGH PENETRATIONS |
| | OF FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL |
| | COMPLY WITH SECTION 713.4.1.1.1 OR 713.4.1.1.2. |
| | 24) PLEASE PROVIDE WHERE THE FOLLOWING REQUIREMENTS FOR |
| | HIGH RISE CONSTRUCTION CAN BE FOUND: |
| | 24A)FBC-B 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS. |
| | REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO |
| | A MINIMUM OF TWO WATER MAINS LOCATED IN DIFFERENT |
| | STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED |
| | BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE |
| | PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN |
| | THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY |
| | THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO |
| | OPERATE. |
| | |
| | 24B) FBC-B [F] 403.4.3 EMERGENCY VOICE/ALARM |
| | COMMUNICATION SYSTEM. |
| | AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. |
| | |
| | 24C) FBC-B [F] 403.4.4 EMERGENCY RESPONDER RADIO |
| | COVERAGE. |
| | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 24D) FBC-B 403.4.6 SMOKE REMOVAL. SMOKE CONTROL SHALL |
| | BE PROVIDED IN ACCORDANCE WITH SECTION 909. |
| | |
| | |
| | 24E) FBC-B [F] 403.4.7 STANDBY POWER. |
| | A STANDBY POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL |
| | BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN |
| | SECTION 403.4.7.2. |
| | |
| | 24F) FBC-B [F] 403.4.7.2 STANDBY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: |
| | 1. POWER AND LIGHTING FOR THE FIRE COMMAND CENTER |
| | REQUIRED BY SECTION 403.4.5; |
| | 2. VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT |
| | FOR SMOKEPROOF ENCLOSURES; AND |
| | 3. STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| | ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008. |
| | |
| | 24G) [F] 403.4.8 EMERGENCY POWER SYSTEMS. AN EMERGENCY |
| | POWER SYSTEM COMPLYING WITH CHAPTER 27 SHALL BE |
| | PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED IN SECTION |
| | 403.4.8.1. |
| | [F] 403.4.8.1 EMERGENCY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| | 1. EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION REQUIRED |
| | BY CHAPTER 10; |
| | 2. ELEVATOR CAR LIGHTING; |
| | 3. EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; |
| | 4. AUTOMATIC FIRE DETECTION SYSTEMS; |
| | 5. FIRE ALARM SYSTEMS; AND |
| | 6. ELECTRICALLY POWERED FIRE PUMPS. |
| | |
| | |
| | 24H) FBC-B 403.5.3.1 STAIRWAY COMMUNICATION SYSTEM. |
| | A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| | CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| | SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| | EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE |
| | LOCKED. |
| | |
| | 24I) FBC-B 403.5.4 SMOKEPROOF EXIT ENCLOSURES. EVERY |
| | REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET |
| | (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| | VEHICLE ACCESS SHALL COMPLY WITH SECTIONS 909.20 AND |
| | 1022.9. |
| | 24J) FBC-B 1022.8 FLOOR IDENTIFICATION SIGNS. / |
| | 1022.8.1 SIGNAGE REQUIREMENTS. |
| | |
| | 24K) FBC-B 403.5.5 LUMINOUS EGRESS PATH MARKINGS. |
| | LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 1024.1-5. |
| | 1024.4 SELF-LUMINOUS AND PHOTOLUMINESCENT. LUMINOUS |
| | EGRESS PATH MARKINGS SHALL BE PERMITTED TO BE MADE OF |
| | ANY MATERIAL, INCLUDING PAINT, PROVIDED THAT AN |
| | ELECTRICAL CHARGE IS NOT REQUIRED TO MAINTAIN THE |
| | REQUIRED LUMINANCE. SUCH MATERIALS SHALL INCLUDE, BUT |
| | ARE NOT LIMITED TO, SELF-LUMINOUS MATERIALS AND |
| | PHOTOLUMINESCENT MATERIALS. MATERIALS SHALL COMPLY WITH |
| | EITHER: |
| | 1. UL 1994; OR |
| | 2. ASTM E 2072, EXCEPT THAT THE CHARGING SOURCE SHALL |
| | BE 1 FOOTCANDLE (11 LUX) OF FLUORESCENT ILLUMINATION |
| | FOR 60 MINUTES, AND THE MINIMUM LUMINANCE SHALL BE 30 |
| | MILLICANDELAS PER SQUARE METER AT 10 MINUTES AND 5 |
| | MILLICANDELAS PER SQUARE METER AFTER 90 MINUTES. |
| | |
| | 1024.5 ILLUMINATION.EXIT ENCLOSURES WHERE |
| | PHOTOLUMINESCENT EXIT PATH MARKINGS ARE INSTALLED SHALL |
| | BE PROVIDED WITH THE MINIMUM MEANS OF EGRESS |
| | ILLUMINATION REQUIRED BY SECTION 1006 FOR AT LEAST 60 |
| | MINUTES PRIOR TO PERIODS WHEN THE BUILDING IS OCCUPIED. |
| | |
| | 25) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO |
| | HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE |
| | STANDPIPE SHALL BE PROVIDED FOR USE DURING |
| | CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN |
| | THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET |
| | (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE |
| | DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE |
| | PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT |
| | ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| | STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| | TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| | CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| | |
| | 26) [F] 3312.1 COMPLETION BEFORE OCCUPANCY. |
| | IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY |
| | ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED |
| | AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3. |
| | |
| | 27) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 28) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | |
| | 29) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 30) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |