| 2015-06-27 14:37:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- REVISE BUILDING EXPOSURE AND ALL DESIGN PRESSURES. |
| | 2- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE |
| | OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND |
| | OFFICE. SEC. R302.5. |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR (NOTE: ALL |
| | PRODUCT APPROVALS WILL BE RE-REVIEWED WHEN ALL DESIGN |
| | PRESSURES ARE REVISED). |
| | A) CUSTOM MADE ENTRY DOOR ASSEMBLY. NEED TO PROVIDE |
| | COMPLETE ENGINEER PACKAGE FOR BUILDING OFFICIAL |
| | REVIEW/APPROVAL. CONTACT ROBERT BROWN (BUILDING |
| | OFFICIAL) AT [email protected]. |
| | B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE |
| | WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER |
| | THAT SIZE. |
| | NOTE: WINDOW SCHEDULE CALLS FOR PGT WINDOWS. PRODUCT |
| | APPROVALS SUBMITTED ARE FOR DIFFERENT MANUFACTURER. |
| | REVISE AS REQUIRED. |
| | C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. |
| | D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED |
| | FOR DOOR #3. |
| | E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA |
| | 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS. |
| | 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
| | 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE |
| | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 F.S. |
| | |
| | NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| | REQUIRED DURING CONSTRUCTION. |