| Plan Review Notes For Permit 15031260 |
| Permit Number |
15031260 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-20 14:20:31 | NOTE: THIS MAY BE A PROVISO TO PROVIDE COMPLETE REVISED | | | INFORMATION (CALCULATIONS AND A/C PLANS) UNDER A | | | SEPARATE PERMIT. | | | | | | 1- SELECTED EQUIPMENT EXCEEDS THE CALCULATED TOTAL | | | LOAD. NEED TO COMPLY WITH SEC. 403.6.1.1 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 2- NEED TO PROVIDE MECHANICAL VENTILATION FOR CABANA | | | BATHROOM AND SAUNA ROOM. SEC. R303 AND M1507 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|