| Plan Review Notes For Permit 15031260 |
| Permit Number |
15031260 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-25 11:39:10 | 4/28/2015 | | | PROJECT: POTTER RESIDENCE | | | PERMIT#: 15031260 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN | | | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | 1) REVISE THE RISER DIAGRAM TO INDICATE THE | | | INSTALLATION OF THE INTER-SYSTEM BONDING DEVICE. SEE | | | NEC 250.94 | | | | | | 2) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED AT | | | THE SECOND FLOOR ACCESS TO THE ATTIC WHERE AHU2 AND | | | AHU3 ARE INSTALLED TO GIVE SAFE ACCESS TO THE WORKING | | | SPACE AROUND ELECTRICAL EQUIPMENT INSTALLED IN ATTIC. | | | NEC 110.33(B) | | | | | | PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS | | | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND | | | SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS | | | SUCH AS BUT NOT LIMITED TO THE FOLLOWING: | | | DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|