Plan Review Notes
Plan Review Notes For Permit 15031260
Permit Number 15031260
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-25 11:39:104/28/2015
 PROJECT: POTTER RESIDENCE
 PERMIT#: 15031260
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) REVISE THE RISER DIAGRAM TO INDICATE THE
 INSTALLATION OF THE INTER-SYSTEM BONDING DEVICE. SEE
 NEC 250.94
  
 2) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED AT
 THE SECOND FLOOR ACCESS TO THE ATTIC WHERE AHU2 AND
 AHU3 ARE INSTALLED TO GIVE SAFE ACCESS TO THE WORKING
 SPACE AROUND ELECTRICAL EQUIPMENT INSTALLED IN ATTIC.
 NEC 110.33(B)
  
 PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS
 SUCH AS BUT NOT LIMITED TO THE FOLLOWING:
 DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  