| 2015-05-14 15:24:05 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SELECTED EQUIPMENT EXCEEDS THE CALCULATED TOTAL | | | LOAD. NEED TO COMPLY WITH SEC. 403.6.1.1 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN DOESN'T | | | MATCH EQUIPMENT LISTED ON THE EQUIPMENT SIZING | | | CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. NOTE: COORDINATE WITH ITEM #1 ABOVE WHEN | | | THE EQUIPMENT IS REVISED. | | | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|