| 2015-04-28 12:29:39 | 4/28/2015 |
| | PROJECT: POTTER RESIDENCE |
| | PERMIT#: 15031260 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) THE ELECTRICAL SERVICE LOAD SUMMARY INDICATES A |
| | TOTAL CONNECTED LOAD OF 320AMPS AND YET THE RISER |
| | DIAGRAM INDICATES ONLY A 2/0 FEEDER TO A 200AMP MAIN |
| | RATED PANEL "A". REVISE THE RISER TO ACCOMMODATE THE |
| | TOTAL CONNECTED LOAD PROPOSED. |
| | |
| | 2) REVISE THE RISER DIAGRAM TO INDICATE THE BONDING OF |
| | THE GAS PIPING AND THE INSTALLATION OF THE INTER-SYSTEM |
| | BONDING DEVICE. SEE NEC 250.94 AND 250.104(2) |
| | |
| | 3) INDICATE THE LOCATION FOR THE SAUNA AND PANEL "C" ON |
| | THE FLOOR PLAN.WPB AMENDMENTS TO THE FBC 107.2.1 |
| | |
| | 4) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | NEC 110.33(B) |
| | |
| | 5) RECESSED LUMINARIES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE |
| | BETWEEN CONDITIONED AND UNCONDITIONED SPACES. ALL |
| | RECESSED LUMINARIES SHALL BE IC-RATED AND LABELED AS |
| | MEETING ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) |
| | PRESSURE DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 |
| | L/S) OF AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE |
| | CEILING CAVITY. ALL RECESSED LUMINARIES SHALL BE SEALED |
| | WITH A GASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR |
| | WALL OR CEILING COVERING. FBC-E 502.3.8 RECESSED |
| | LIGHTING. |
| | |
| | 6) VERIFY CARBON MONOXIDE DETECTORS ARE INSTALLED AS |
| | REQUIRED. EVERY SEPARATE BUILDING OR AN ADDITION TO AN |
| | EXISTING BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED AND HAVING A FOSSIL FUEL BURNING |
| | HEATER OR APPLIANCE, A FIRE PLACE, AN ATTACHED GARAGE, |
| | OR OTHER FEATURE, FIXTURE OR ELEMENT THAT EMITS CARBON |
| | MONOXIDE AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN |
| | OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10' |
| | OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| | FBC-RESIDENTIAL 315.1 |
| | |
| | 7) PROVIDE A 3WAY SWITCH AT THE BALCONY EGRESS DOORS |
| | FROM BATH 2 ON THE 2ND FL WPB AMENDMENTS TO THE FBC |
| | 107.2.1 |
| | |
| | 8) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC |
| | 410.16(A) AND (B). |
| | |
| | 9) DOUBLE CHECK AND VERIFY GFI OUTLET SPACING AT THE |
| | KITCHEN COUNTERTOPS. THERE APPEARS TO BE A COUPLE OF |
| | OUTLETS MISSING BY THE REFRIGERATOR AND THE OVEN. NEC |
| | 210.52(C)(1) WALL COUNTERTOP SPACES. |
| | |
| | 10) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC |
| | DISCONNECT. NEC 422.31 |
| | |
| | PLEASE PROVIDE A SEPARATE PERMIT APPLICATIONS |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND |
| | SHOP DRAWINGS FOR ALL LOW VOLTAGE SPECIALTY SYSTEMS |
| | SUCH AS BUT NOT LIMITED TO THE FOLLOWING: |
| | DATA/COMMUNICATION, SECURITY, AND AUDIO/VIDEO. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |