| Date |
Text |
| 2015-04-13 15:30:21 | 4/13/2015 |
| | PROJECT: REHAB 2119 WARE DR |
| | PERMIT#: 15031248 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) VERIFY ALL NEW GENERAL PURPOSE OUTLETS MUST BE |
| | TAMPER RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 2) VERIFY SUFFICIENT ACCESS AND WORKING SPACE SHALL BE |
| | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL PANELS TO |
| | PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| | EQUIPMENT. NEC 110.26 |
| | |
| | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 4) VERIFY RECEPTACLE WITHIN SIGHT OF MECHANICAL |
| | EQUIPMENT. ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. |
| | |
| | 5) VERIFY DISCONNECTS FOR MECHANICAL EQUIPMENT. |
| | DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM |
| | AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR |
| | REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL |
| | BE PERMITTED TO BE INSTALLED ON OR WITHIN THE |
| | AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14 |
| | |
| | 6) VERIFY RECEPTACLE PLACEMENT. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| | M (6 FT) FROM A RECEPTACLE OUTLET. |
| | |
| | 7) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT |
| | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4. |
| | |
| | 8) PROVIDE SMOKE DETECTORS INSIDE AND OUTSIDE OF |
| | SLEEPING AREAS AND A CARBON MONOXIDE DETECTOR WITHIN 10 |
| | OF SLEEPING AREAS. WHEN ALTERATIONS, REPAIRS, OR |
| | ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE |
| | SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. FBC-RESIDENTIAL 314 AND 315. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |