Plan Review Notes
Plan Review Notes For Permit 15031248
Permit Number 15031248
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-13 15:30:214/13/2015
 PROJECT: REHAB 2119 WARE DR
 PERMIT#: 15031248
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) VERIFY ALL NEW GENERAL PURPOSE OUTLETS MUST BE
 TAMPER RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 2) VERIFY SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL PANELS TO
 PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
 EQUIPMENT. NEC 110.26
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) VERIFY RECEPTACLE WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT.
  
 5) VERIFY DISCONNECTS FOR MECHANICAL EQUIPMENT.
 DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM
 AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR
 REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL
 BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 6) VERIFY RECEPTACLE PLACEMENT. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET.
  
 7) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4.
  
 8) PROVIDE SMOKE DETECTORS INSIDE AND OUTSIDE OF
 SLEEPING AREAS AND A CARBON MONOXIDE DETECTOR WITHIN 10
 OF SLEEPING AREAS. WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  