| Notes |
| Date |
Text |
| 2015-07-23 08:27:28 | MECHANICAL PROVISO: 7/23/15. | | | THE PLANS ARE APPROVED WITH EXCEPTION HOWEVER REVISED | | | PLANS TO CORRECT THE FOLLOWING LIST OF DEFICIENCIES | | | SHALL BE SUBMITTED, REVIEWED AND APPROVED PRIOR TO | | | FIRST INSPECTION. | | | | | | 1) PROVIDE OUTDOOR AIR CALCULATIONS FOR ALL OCCUPIED | | | ROOMS AND SPACES IN BUILDINGS A & B- TABLE 403.3. | | | 2) SHOW A MEANS OF PROVIDING THE REQUIRED OUTDOOR AIR | | | TO THE ROOMS AND SPACES. | | | 3) REVISE THE PLANS TO SHOW THAT THE LOCATIONS OF THE | | | CONDENSERS AND ZONE ARRANGEMENTS AS SHOWN ON THE NEW AC | | | PLANS MATCH THE MAIN ARCHITECTURAL AND ELECTRICAL PLAN | | | SETS. PLEASE MAKE THESE PLANS MATCH ONE WAY OR THE | | | OTHER. | | | 4) PROVIDE DUPLICATE SETS OF AC PLANS FOR BUILDINGS A | | | AND B ARE REQUIRED: ONLY ONE SET FOR EACH WAS | | | SUBMITTED. | | | 5) PROVIDE CONDENSATE DISPOSAL DETAILS, PRIMARY AND | | | SECONDARY- SECTION 307 FBC-10 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|