Date Text
2015-07-21 10:31:597/21/2015
 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) COORDINATE THE INSTALLATION OF THE A/C EQUIPMENT AND
 THE TANKLESS WATER HEATERS WITH THE MANUFACTURER'S
 DOCUMENTATION FOR THE MAXIMIM OCPD AND THE MINIMUM
 AMPACITY OF THE CIRCUIT CONDUCTORS FEEING EQUIPMENT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,