| Plan Review Notes For Permit 15031231 |
| Permit Number |
15031231 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-07 08:17:25 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | | | 1) COMMENTS #2, 4, & 5 FROM THE FIRST REVIEW STILL | | | EXIST. AS PREVIOUSLY REQUESTED PROVIDE- A) OUTDOOR AIR | | | CALCULATIONS FOR ALL OCCUPIABLE ROOMS AND SPACES IN | | | BUILDINGS A & B- TABLE 403.3. B) CONDENSATE DISPOSAL | | | DETAILS, PRIMARY AND SECONDARY- SECTION 307. | | | 2) THE LOCATIONS OF THE CONDENSERS AND ZONE | | | ARRANGEMENTS SHOWN ON THE NEW AC PLANS DO NOT MATCH | | | WITH THE MAIN ARCHITECTURAL AND ELECTRICAL PLAN SETS. | | | PLEASE MAKE THESE PLANS MATCH ONE WAY OR THE OTHER. | | | 3) THE AC PLANS DO NOT SHOW ANY MEANS OF PROVIDING | | | OUTDOOR AIR INTO THE ROOMS AND SPACES. | | | 4) PLEASE NOTE THAT ONLY ONE SET OF AC PLANS WERE | | | SUBMITTED FOR BUILDINGS A AND B: DUPLICATE SETS ARE | | | REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|