2015-07-07 08:17:252ND REVIEW: FBC 2010 MECHANICAL
  
 1) COMMENTS #2, 4, & 5 FROM THE FIRST REVIEW STILL
 EXIST. AS PREVIOUSLY REQUESTED PROVIDE- A) OUTDOOR AIR
 CALCULATIONS FOR ALL OCCUPIABLE ROOMS AND SPACES IN
 BUILDINGS A & B- TABLE 403.3. B) CONDENSATE DISPOSAL
 DETAILS, PRIMARY AND SECONDARY- SECTION 307.
 2) THE LOCATIONS OF THE CONDENSERS AND ZONE
 ARRANGEMENTS SHOWN ON THE NEW AC PLANS DO NOT MATCH
 WITH THE MAIN ARCHITECTURAL AND ELECTRICAL PLAN SETS.
 PLEASE MAKE THESE PLANS MATCH ONE WAY OR THE OTHER.
 3) THE AC PLANS DO NOT SHOW ANY MEANS OF PROVIDING
 OUTDOOR AIR INTO THE ROOMS AND SPACES.
 4) PLEASE NOTE THAT ONLY ONE SET OF AC PLANS WERE
 SUBMITTED FOR BUILDINGS A AND B: DUPLICATE SETS ARE
 REQUIRED.
  