| Plan Review Notes For Permit 15031231 |
| Permit Number |
15031231 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-07 12:50:19 | 7/7/2015 | | | PROJECT: BEACHWAY CENTER | | | PERMIT#: 15031231 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) THE RISER DIAGRAM INDICATES SIZE 150MCM WIRE FROM | | | THE METER TO THE MAIN IN PANEL A AND FROM PANEL A TO | | | PANEL A1. PANEL A IS INDICATED TO BE RATED AT 200AMP | | | MAX AND PANEL A1 IS ONLY RATED AT 100AMP. THERE IS NO | | | SIZE 150MCM. PROVIDE AN APPROVED WIRE SIZE FOR THE LOAD | | | TO BE SERVED. | | | | | | 2) THE RISER DIAGRAM INDICATES A 250AMP MAIN BREAKER IN | | | PANEL A. PANEL A IS INDICATED TO BE RATED AT 200AMP | | | MAX. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|