2015-07-07 12:50:197/7/2015
 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE RISER DIAGRAM INDICATES SIZE 150MCM WIRE FROM
 THE METER TO THE MAIN IN PANEL A AND FROM PANEL A TO
 PANEL A1. PANEL A IS INDICATED TO BE RATED AT 200AMP
 MAX AND PANEL A1 IS ONLY RATED AT 100AMP. THERE IS NO
 SIZE 150MCM. PROVIDE AN APPROVED WIRE SIZE FOR THE LOAD
 TO BE SERVED.
  
 2) THE RISER DIAGRAM INDICATES A 250AMP MAIN BREAKER IN
 PANEL A. PANEL A IS INDICATED TO BE RATED AT 200AMP
 MAX.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]