| 2015-05-16 08:38:51 | PLAN DENIED | | | 1) PROVIDE A EQUIPMENT SCHEDULE FOR | | | AIR CONDITIONING EQUIPMENT. PER SECTION | | | 107 FBC 2010 | | | 2) PROVIDE FRESH AIR CALCULATIONS ON | | | THE PLAN PER TABLE 403.3 MINIMUM | | | VENTILATION RATES FBC (M) 2010 | | | 3) SHOW BATHROOM EXHAUST ON THE PLAN | | | PER TABLE 401.3 AND EXHAUST TERMINATION | | | 4) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL | | | SHOW TERMINATION OF CONDENSATE. | | | 5) REFER TO SECTION 307.2.3 AUXILIARY AND | | | SECONDARY DRAIN SYSTEMS. 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | |
|