 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A RISER DIAGRAM AND LOAD CALCULATION FOR
 BOTH BUILDINGS. IF REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE
 PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH
 A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER,
 THE TOTAL CALCULATED LOAD BEFORE APPLYING DEMAND
 FACTORS, THE DEMAND FACTORS USED, THE CALCULATED LOAD
 AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED. NEC 215.5. WPB AMENDMENTS TO FBC
 107.3.5.1.2
  
 2) BUILDING A INDICATES A SYMBOL FOR A RECEPTACLE IN
 THE CENTER OF EXISTING ROOM 2. PLEASE INDICATE A
 PURPOSE FOR THIS DEVICE AND WEATHER IT IS TO BE LOCATED
 IN THE CEILING OR THE FLOOR. IF IT IS TO BE LOCATED IN
 THE FLOOR, THE BOXES SHALL BE LISTED SPECIFICALLY FOR
 THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED
 IN THE FLOOR. NEC 314.27(C)
  
 3) AS NOTED ON THE FIRE INSPECTORS COMMENTS, A SMOKE
 DETECTOR SHALL BE INSTALLED IN EACH OF THE NEWLY
 CREATED SLEEPING ROOMS.
  
 4) PROVIDE THE MANUFACTURER DOCUMENTATION FOR THE A/C
 SYSTEMS TO INCLUDE THE WIRING DIAGRAMS AND CIRCUITRTY
 REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  