| 2015-05-15 09:32:35 | 5/15/2015 |
| | PROJECT: BEACHWAY CENTER |
| | PERMIT#: 15031231 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A RISER DIAGRAM AND LOAD CALCULATION FOR |
| | BOTH BUILDINGS. IF REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE |
| | PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH |
| | A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE |
| | BUILDING OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, |
| | THE TOTAL CALCULATED LOAD BEFORE APPLYING DEMAND |
| | FACTORS, THE DEMAND FACTORS USED, THE CALCULATED LOAD |
| | AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF |
| | CONDUCTORS TO BE USED. NEC 215.5. WPB AMENDMENTS TO FBC |
| | 107.3.5.1.2 |
| | |
| | 2) BUILDING A INDICATES A SYMBOL FOR A RECEPTACLE IN |
| | THE CENTER OF EXISTING ROOM 2. PLEASE INDICATE A |
| | PURPOSE FOR THIS DEVICE AND WEATHER IT IS TO BE LOCATED |
| | IN THE CEILING OR THE FLOOR. IF IT IS TO BE LOCATED IN |
| | THE FLOOR, THE BOXES SHALL BE LISTED SPECIFICALLY FOR |
| | THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED |
| | IN THE FLOOR. NEC 314.27(C) |
| | |
| | 3) AS NOTED ON THE FIRE INSPECTORS COMMENTS, A SMOKE |
| | DETECTOR SHALL BE INSTALLED IN EACH OF THE NEWLY |
| | CREATED SLEEPING ROOMS. |
| | |
| | 4) PROVIDE THE MANUFACTURER DOCUMENTATION FOR THE A/C |
| | SYSTEMS TO INCLUDE THE WIRING DIAGRAMS AND CIRCUITRTY |
| | REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |