| Date |
Text |
| 2015-04-10 13:53:35 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031231 |
| | ADD: 2901 BROADWAY |
| | CONT: J M PROPERTIES |
| | TEL: (561)804-1248 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY APRIL 10/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS SHEET A1.1 INDICATE THE FACILITY IS |
| | LOCATED IN PALM BEACH GARDENS. SEE THE HEADING |
| | STATISTICS. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| | PROJET. |
| | |
| | 2) THE COVER SHEET LIST THE OCCUPANCY AS A I-2. THE |
| | 2010 FBC-B SECTION LIST A I-2 OCCUPANCY AS : THIS |
| | OCCUPANCY SHALL INCLUDE BUILDINGS AND STRUCTURES USED |
| | FOR MEDICAL, SURGICAL, PSYCHIATRIC, NURSING OR |
| | CUSTODIAL CARE FOR PERSONS WHO ARE NOT CAPABLE OF |
| | SELF-PRESERVATION. FROM THE MEETING MONTHS AGO I |
| | BELIEVE THE GROUP I-1 OCCUPANCY IS A BETTER FIT FOR |
| | TYPE OF OCCUPANCY. THIS OCCUPANCY SHALL INCLUDE |
| | BUILDINGS, STRUCTURES OR PARTS THEREOF HOUSING MORE |
| | THAN 16 PERSONS, ON A 24-HOUR BASIS, WHO BECAUSE OF |
| | AGE, MENTAL DISABILITY OR OTHER REASONS, LIVE IN A |
| | SUPERVISED RESIDENTIAL ENVIRONMENT THAT PROVIDES |
| | PERSONAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF |
| | RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL |
| | ASSISTANCE FROM STAFF. |
| | |
| | PERSONNAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF |
| | RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL |
| | ASSISTANCE FROM STAFF. THIS CLASSIFICATION SHALL |
| | INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: |
| | RESIDENTIAL BOARD AND CARE FACILITIES, ASSISTED LIVING |
| | FACILITIES, HALFWAY HOUSES, GROUP HOMES, CONGREGATE |
| | CARE FACILITIES, SOCIAL REHABILITATION FACILITIES, |
| | ALCOHOL AND DRUG ABUSE CENTERS AND CONVALESCENT |
| | FACILITIES. |
| | |
| | THIS REVIEW WILL BE COMPLETED AS A TYPE I-1 OCCUPANCY |
| | WITH COMMENTS. PLANS DO NOT STATE IF THIS IS A CHANGE |
| | OF OCCUPANCY OR NOT? |
| | |
| | 3) THE COVER SHEET DOES NOT STATE THAT THE BUILDINGS |
| | ARE TO BE FIRE SPRINKLERED, SHOW COMPLIANCE WITH [F] |
| | 903.2.6 GROUP I. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | PROVIDED THROUGHOUT BUILDINGS WITH A GROUP I FIRE AREA. |
| | EXCEPTION: AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.2 OR 903.3.1.3 SHALL BE |
| | ALLOWED IN GROUP I-1 FACILITIES. |
| | |
| | 4) SHEET A2.2THE FLOOR PLAN DOES NOT SHOW COMPLIANCE |
| | WITH FBC-B 439.2 SEPARATION WALLS. WALLS SEPARATING |
| | DWELLING UNITS IN THE SAME BUILDING, WALLS SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND WALLS |
| | SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER |
| | OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING |
| | SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE |
| | WITH SECTION 709. |
| | |
| | 5) THE PLANS DO NOT SHOW COMPLIANCE WITH FBC-B TABLE |
| | 803.9 INTERIOR WALL & CEILING FINISH REQUIREMENTS BY |
| | OCCUPANCY. |
| | |
| | 6) PLEASE PROVIDE DOCUMENTATION WITH FBC-B IN GROUPS |
| | I-1 AND I-2, COMBUSTIBLE DECORATIVE MATERIALS SHALL |
| | MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701 UNLESS |
| | THE DECORATIVE MATERIALS, INCLUDING, BUT NOT LIMITED |
| | TO, PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED |
| | QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD |
| | IS NOT PRESENT. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC-B F] 907.2.6.1 GROUP I-1. |
| | AN AUTOMATIC SMOKE DETECTION SYSTEM SHALL BE INSTALLED |
| | IN CORRIDORS, WAITING AREAS OPEN TO CORRIDORS AND |
| | HABITABLE SPACES OTHER THAN SLEEPING UNITS AND |
| | KITCHENS. THE SYSTEM SHALL BE ACTIVATED IN ACCORDANCE |
| | WITH SECTION 907.5. |
| | |
| | 8) SHEET A2.4 DETAIL B7 IT APPEARS THERE IS A CURB BUT |
| | THE DETAIL IS LABELED AS A ROLL-IN SHOWER? |
| | |
| | 9) SHEET A2.2 SHOWS THE BEDROOM # 7 WITH THE ACCESSIBLE |
| | BATHROOM. THE PLANS DO NOT SHOW HOW COMPLIANCE WITH |
| | 2010 FBC-ACCESSIBILITY CODE 223.2.1. WILL BE ACHIEVED. |
| | 223.2.1 FACILITIES NOT SPECIALIZING IN TREATING |
| | CONDITIONS THAT AFFECT MOBILITY. |
| | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER |
| | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE |
| | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS |
| | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. |
| | |
| | 805.1 GENERAL. |
| | MEDICAL CARE FACILITY AND LONG-TERM CARE FACILITY |
| | PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO PROVIDE |
| | MOBILITY FEATURES SHALL COMPLY WITH 805. |
| | |
| | 805.2 TURNING SPACE. |
| | TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED |
| | WITHIN THE ROOM. |
| | |
| | 805.3 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 SHALL BE |
| | PROVIDED ON EACH SIDE OF THE BED. THE CLEAR FLOOR SPACE |
| | SHALL BE POSITIONED FOR PARALLEL APPROACH TO THE SIDE |
| | OF THE BED. |
| | |
| | 805.4 TOILET AND BATHING ROOMS. |
| | TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A |
| | PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH |
| | 603. WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET, |
| | ONE LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY |
| | WITH THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610. |
| | |
| | 10) SHEET A2.2 DOES NOT SHOW ANY DINKING FOUNTAINS, |
| | WITH THE OCCUPANT LOAD GREATER THAN 15 THE PLUMBING |
| | CODE WILL REQUIRE 1. PLEASE SEE FL ACCESSIBILITY CODE |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 11) SHEET A2.2 THE OFFICE DOES NOT INDICATE COMPLIANCE |
| | WITH ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES. |
| | WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| | WITH 902.3. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |