Plan Review Notes
Plan Review Notes For Permit 15031231
Permit Number 15031231
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-10 13:53:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031231
 ADD: 2901 BROADWAY
 CONT: J M PROPERTIES
 TEL: (561)804-1248
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: FRIDAY APRIL 10/2015
 ACTION: DENIED
  
 1) THE PLANS SHEET A1.1 INDICATE THE FACILITY IS
 LOCATED IN PALM BEACH GARDENS. SEE THE HEADING
 STATISTICS. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJET.
  
 2) THE COVER SHEET LIST THE OCCUPANCY AS A I-2. THE
 2010 FBC-B SECTION LIST A I-2 OCCUPANCY AS : THIS
 OCCUPANCY SHALL INCLUDE BUILDINGS AND STRUCTURES USED
 FOR MEDICAL, SURGICAL, PSYCHIATRIC, NURSING OR
 CUSTODIAL CARE FOR PERSONS WHO ARE NOT CAPABLE OF
 SELF-PRESERVATION. FROM THE MEETING MONTHS AGO I
 BELIEVE THE GROUP I-1 OCCUPANCY IS A BETTER FIT FOR
 TYPE OF OCCUPANCY. THIS OCCUPANCY SHALL INCLUDE
 BUILDINGS, STRUCTURES OR PARTS THEREOF HOUSING MORE
 THAN 16 PERSONS, ON A 24-HOUR BASIS, WHO BECAUSE OF
 AGE, MENTAL DISABILITY OR OTHER REASONS, LIVE IN A
 SUPERVISED RESIDENTIAL ENVIRONMENT THAT PROVIDES
 PERSONAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF
 RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL
 ASSISTANCE FROM STAFF.
  
 PERSONNAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF
 RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL
 ASSISTANCE FROM STAFF. THIS CLASSIFICATION SHALL
 INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
 RESIDENTIAL BOARD AND CARE FACILITIES, ASSISTED LIVING
 FACILITIES, HALFWAY HOUSES, GROUP HOMES, CONGREGATE
 CARE FACILITIES, SOCIAL REHABILITATION FACILITIES,
 ALCOHOL AND DRUG ABUSE CENTERS AND CONVALESCENT
 FACILITIES.
  
 THIS REVIEW WILL BE COMPLETED AS A TYPE I-1 OCCUPANCY
 WITH COMMENTS. PLANS DO NOT STATE IF THIS IS A CHANGE
 OF OCCUPANCY OR NOT?
  
 3) THE COVER SHEET DOES NOT STATE THAT THE BUILDINGS
 ARE TO BE FIRE SPRINKLERED, SHOW COMPLIANCE WITH [F]
 903.2.6 GROUP I. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT BUILDINGS WITH A GROUP I FIRE AREA.
 EXCEPTION: AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.2 OR 903.3.1.3 SHALL BE
 ALLOWED IN GROUP I-1 FACILITIES.
  
 4) SHEET A2.2THE FLOOR PLAN DOES NOT SHOW COMPLIANCE
 WITH FBC-B 439.2 SEPARATION WALLS. WALLS SEPARATING
 DWELLING UNITS IN THE SAME BUILDING, WALLS SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND WALLS
 SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 709.
  
 5) THE PLANS DO NOT SHOW COMPLIANCE WITH FBC-B TABLE
 803.9 INTERIOR WALL & CEILING FINISH REQUIREMENTS BY
 OCCUPANCY.
  
 6) PLEASE PROVIDE DOCUMENTATION WITH FBC-B IN GROUPS
 I-1 AND I-2, COMBUSTIBLE DECORATIVE MATERIALS SHALL
 MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701 UNLESS
 THE DECORATIVE MATERIALS, INCLUDING, BUT NOT LIMITED
 TO, PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED
 QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD
 IS NOT PRESENT.
  
 7) SHOW COMPLIANCE WITH FBC-B F] 907.2.6.1 GROUP I-1.
 AN AUTOMATIC SMOKE DETECTION SYSTEM SHALL BE INSTALLED
 IN CORRIDORS, WAITING AREAS OPEN TO CORRIDORS AND
 HABITABLE SPACES OTHER THAN SLEEPING UNITS AND
 KITCHENS. THE SYSTEM SHALL BE ACTIVATED IN ACCORDANCE
 WITH SECTION 907.5.
  
 8) SHEET A2.4 DETAIL B7 IT APPEARS THERE IS A CURB BUT
 THE DETAIL IS LABELED AS A ROLL-IN SHOWER?
  
 9) SHEET A2.2 SHOWS THE BEDROOM # 7 WITH THE ACCESSIBLE
 BATHROOM. THE PLANS DO NOT SHOW HOW COMPLIANCE WITH
 2010 FBC-ACCESSIBILITY CODE 223.2.1. WILL BE ACHIEVED.
 223.2.1 FACILITIES NOT SPECIALIZING IN TREATING
 CONDITIONS THAT AFFECT MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 805.1 GENERAL.
 MEDICAL CARE FACILITY AND LONG-TERM CARE FACILITY
 PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES SHALL COMPLY WITH 805.
  
 805.2 TURNING SPACE.
 TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED
 WITHIN THE ROOM.
  
 805.3 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 SHALL BE
 PROVIDED ON EACH SIDE OF THE BED. THE CLEAR FLOOR SPACE
 SHALL BE POSITIONED FOR PARALLEL APPROACH TO THE SIDE
 OF THE BED.
  
 805.4 TOILET AND BATHING ROOMS.
 TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A
 PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH
 603. WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET,
 ONE LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY
 WITH THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 10) SHEET A2.2 DOES NOT SHOW ANY DINKING FOUNTAINS,
 WITH THE OCCUPANT LOAD GREATER THAN 15 THE PLUMBING
 CODE WILL REQUIRE 1. PLEASE SEE FL ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 11) SHEET A2.2 THE OFFICE DOES NOT INDICATE COMPLIANCE
 WITH ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved