2015-04-16 09:57:04APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION FEE(S
  
 1) FBC 2704 BONDING METAL FRAMING MEMBERS:
 METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT
 GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE
 THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE NEC
 TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, A
 GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING SHALL
 BE PERMITTED.
  
 2) FBC-RESIDENTIAL 314 AND 315.
 VERIFY SMOKE AND CARBON MONIXIDE DETECTORS ARE
 INSTALLED AS REQUIRED. WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 3) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) NEC 210.8
 ALL OUTLETS IN THE KITCHEN TO BE GFI. NEC 210.8
  