| Plan Review Notes For Permit 15031160 |
| Permit Number |
15031160 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-04-16 09:57:04 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION FEE(S | | | | | | 1) FBC 2704 BONDING METAL FRAMING MEMBERS: | | | METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT | | | GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE | | | THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE NEC | | | TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, A | | | GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING SHALL | | | BE PERMITTED. | | | | | | 2) FBC-RESIDENTIAL 314 AND 315. | | | VERIFY SMOKE AND CARBON MONIXIDE DETECTORS ARE | | | INSTALLED AS REQUIRED. WHEN ALTERATIONS, REPAIRS, OR | | | ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE | | | SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING | | | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE | | | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW | | | DWELLINGS. FBC-RESIDENTIAL 314 AND 315. | | | | | | 3) NEC 210.12, 406.11 | | | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | | | 4) NEC 210.8 | | | ALL OUTLETS IN THE KITCHEN TO BE GFI. NEC 210.8 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|