 PROJECT: HAVENBROOK RESIDENCE
 PERMIT#: 15031147
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS!
  
 IMORTANT NOTICE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE
 TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY
 DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A
 REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN
 OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION
 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE
 BEEN SIGNED BY THE DESIGNER OF RECORD.
  
 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME
 SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO
 NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315.
 SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND
 OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED
 INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE
 ONLY.
  
 3.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6
 FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP
 PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A
 NEW 150AMP ELECTRICAL SERVICE FEEDING A 150 AMP INDOOR
 MAIN LUG PANEL ONLY. REVISE THE RISER DIAGRAM TO
 INCLUDE THE SUB-PANEL INDICATING THE CONDUIT AND WIRE
 SIZES FROM THE MAIN SERVICE TO THE SUB-PANEL.
  
 4) NEC 408.4 PROVIDE A PANEL SCHEDULE FOR THE
 SUB-PANEL. INCLUDE ALL CIRCUIT NAMES AND NUMBERS AS
 WELL AS ALL CIRCUIT OCPD'S AND WIRE SIZES.
  
 5) REVISE PANEL SCHEDULE. AHU AND CU FOR A/C ARE
 240VOLT 2POLE CIRCUITS BUT SHOWN IN THE PANEL SCHEDULE
 SUBMITTED AS SINGLE POLE 120 VOLT CIRCUITS.
 ADDITIONALLY, INCLUDE A CIRCUIT FOR THE WATER HEATER.
  
 6) A MINIMUM OF TWO RECEPTACLES ARE REQUIRED IN THE
 KITCHEN. THERE IS ONLY ONE SHOWN.
  
 7) ADDITIONALLY, A SEPARATE PERMIT APPLICATION
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR
 CONDITIONING SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,