| | PROJECT: HAVENBROOK RESIDENCE |
| | PERMIT#: 15031147 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE COMMENTS! |
| | |
| | IMORTANT NOTICE: |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| | FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE |
| | TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY |
| | DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A |
| | REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN |
| | OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION |
| | 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE |
| | BEEN SIGNED BY THE DESIGNER OF RECORD. |
| | |
| | 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN |
| | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND |
| | 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME |
| | SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO |
| | NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315. |
| | SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND |
| | OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED |
| | INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE |
| | ONLY. |
| | |
| | 3.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6 |
| | FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP |
| | PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A |
| | NEW 150AMP ELECTRICAL SERVICE FEEDING A 150 AMP INDOOR |
| | MAIN LUG PANEL ONLY. REVISE THE RISER DIAGRAM TO |
| | INCLUDE THE SUB-PANEL INDICATING THE CONDUIT AND WIRE |
| | SIZES FROM THE MAIN SERVICE TO THE SUB-PANEL. |
| | |
| | 4) NEC 408.4 PROVIDE A PANEL SCHEDULE FOR THE |
| | SUB-PANEL. INCLUDE ALL CIRCUIT NAMES AND NUMBERS AS |
| | WELL AS ALL CIRCUIT OCPD'S AND WIRE SIZES. |
| | |
| | 5) REVISE PANEL SCHEDULE. AHU AND CU FOR A/C ARE |
| | 240VOLT 2POLE CIRCUITS BUT SHOWN IN THE PANEL SCHEDULE |
| | SUBMITTED AS SINGLE POLE 120 VOLT CIRCUITS. |
| | ADDITIONALLY, INCLUDE A CIRCUIT FOR THE WATER HEATER. |
| | |
| | 6) A MINIMUM OF TWO RECEPTACLES ARE REQUIRED IN THE |
| | KITCHEN. THERE IS ONLY ONE SHOWN. |
| | |
| | 7) ADDITIONALLY, A SEPARATE PERMIT APPLICATION |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND |
| | SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR |
| | CONDITIONING SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |