Plan Review Notes
Plan Review Notes For Permit 15031147
Permit Number 15031147
Review Stop E
Sequence Number 2
Notes
Date Text
2015-04-20 10:42:24SECOND REVIEW: DUPLICATE COMMENTS
 PLEASE PROVIDE PLANS AND INFORMATION TO ADDRESS THE
 FOLLOWING ELECTRICAL REVIEW COMMENTS AS PREVIOUSLY
 REQUESTED.
  
 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY
 DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A
 REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN
 OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION
 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE
 BEEN SIGNED BY THE DESIGNER OF RECORD.
  
 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME
 SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO
 NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315.
 SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND
 OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED
 INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE
 ONLY.
  
 3.) N.E.C. 210.63, AND N.E.C. 210.8 (A) (3). LOCATION
 OF GFCI PROTECTED OUTLET WITHIN 25' OF A.C. CONDENSOR.
 CODE REFFERENCES:
 (A) NEC 210.63 ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP
 GFI RECEPTACLE OUTLET SHALL BE INSTALLED AT AN
 ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE ALSO NEC
 210.8(A)(3),
 (B) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (A) DWELLING UNITS. ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
 (C) NEC 406.8(B)(1) ALL 15 AND 20AMP 125V AND 250V
 RECEPTACLES INSTALLED IN IN A WET LOCATION SHALL HAVE
 AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15- AND 20-AMPERE,
 125- AND 250-VOLT NON-LOCKING RECEPTACLES SHALL BE
 LISTED WEATHER-RESISTANT TYPE
 PLEASE INDICATE ON THE PLANS THAT THE REQUIRED
 RECEPTACLE IS EITHER CURRENTLY EXISTING TO REMAIN OR
 PROPOSED TO BE INSTALLED.
  
 4.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6
 FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP
 PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A
 NEW 150AMP ELECTRICAL SERVICE FEEDING A 60AMP INDOOR
 MAIN LUG ONLY PANEL WITHOUT THE INDICATION OF ANY
 OVERCURRENT PROTECTIVE DEVICE AHEAD OF THE #6 WIRE
 SHOWN ON THE RISER DIAGRAM. A PANEL SCHEDULE IS
 REQUIRED TO INDICATE THE CORRECT OCPD IN THE NEW
 SERVICE EQUIPMENT TO PROTECT THE #6 FEEDER TO THE MAIN
 LUG PANEL IN THE HOUSE.
 5. WIRE SIZE TO 5KW AHU.
  
 5) ADDITIONALLY, A SEPARATE PERMIT APPLICATION
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR
 CONDITIONING SYSTEM.
  