| 2015-03-30 15:26:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| | AND COMPLIANCE. |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS |
| | RETURNED. |
| | |
| | 2. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS SIDE. |
| | |
| | THUMB-TURN LOCK, IRF USED, SHALL BE EQUIPPED WITH AN |
| | ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| | OR SIMILAR). |
| | |
| | 3. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| | ALL OTHER APPLICABLE CODES OR STANDARDS |
| | |