| Plan Review Notes For Permit 15031111 |
| Permit Number |
15031111 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-28 09:04:38 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) CLEARLY SPECIFY SCOPE OF WORK. IF PLUMBING FIXTURES | | | ARE BEING ADDED OR RELOCATED, THEN TWO COPIES OF A | | | PLUMBING RISER DIAGRAM SPECIFY THE SIZES OF THE DRAIN, | | | WASTE AND VENT PIPING IS REQUIRED. FBC 107.3.5.3 | | | |
|