2015-03-31 08:43:06APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 THE RISER DIAGRAM SHOWS THE NEUTRAL CONDUCTOR IS
 SMALLER THAN THE UNGROUNDED CONDUCTORS FOR THE METER TO
 THE PANEL. PROVIDE THE UNBALANCED LOAD CALCULATIONS
 REQUIRED BY NEC 220.61 TO THE FIELD INSPECTOR.
  