| 2015-03-31 08:43:06 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | | | | THE RISER DIAGRAM SHOWS THE NEUTRAL CONDUCTOR IS | | | SMALLER THAN THE UNGROUNDED CONDUCTORS FOR THE METER TO | | | THE PANEL. PROVIDE THE UNBALANCED LOAD CALCULATIONS | | | REQUIRED BY NEC 220.61 TO THE FIELD INSPECTOR. | | | |
|