| 2015-03-30 17:49:12 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATION OPENINGS SHALL HAVE A |
| | LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 |
| | INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A |
| | LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING, |
| | HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS |
| | HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM |
| | AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING |
| | MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION |
| | R802.7. |
| | EXCEPTION: ATTIC SPACES, DESIGNED BY A PROFESSIONAL |
| | ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE |
| | STATE, DESIGNED TO ELIMINATE THE ATTIC VENTING. |
| | FLAT ROOFS ARE NOT EXEMPT FROM VENTING REQUIREMENTS, |
| | UNLESS DESIGNED AS REQUIRED BY THE EXCEPTION. SUBMIT |
| | TWO SETS OF A SIGNED AND SEALED DRAWINGS WITH A WALL |
| | SECTION SHOWING THE LOCATION OF THE INSULATION. |
| | UNVENTED ATTICS ARE PART OF THE CONDITIONED SPACE. THE |
| | APPROVED DRAWINGS SPECIFY SPRAY FOAM INSULATION APPLIED |
| | TO THE UNDERSIDE OF THE ROOF DECK. |
| | |
| | 2) SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS FOR |
| | THE STRUCTURAL ROOF FRAMING AT THE SKYLIGHT OPENING. |
| | SHOW ALL CONNECTORS AND HANGERS. SPECIFY THE SIZE AND |
| | LOCATION OF THE SKYLIGHT OPENING ON THE PLANS. FBC |
| | 107.2.1 & 301.1 |
| | |