2015-03-30 17:49:12PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATION OPENINGS SHALL HAVE A
 LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4
 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A
 LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.7.
 EXCEPTION: ATTIC SPACES, DESIGNED BY A PROFESSIONAL
 ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE
 STATE, DESIGNED TO ELIMINATE THE ATTIC VENTING.
 FLAT ROOFS ARE NOT EXEMPT FROM VENTING REQUIREMENTS,
 UNLESS DESIGNED AS REQUIRED BY THE EXCEPTION. SUBMIT
 TWO SETS OF A SIGNED AND SEALED DRAWINGS WITH A WALL
 SECTION SHOWING THE LOCATION OF THE INSULATION.
 UNVENTED ATTICS ARE PART OF THE CONDITIONED SPACE. THE
 APPROVED DRAWINGS SPECIFY SPRAY FOAM INSULATION APPLIED
 TO THE UNDERSIDE OF THE ROOF DECK.
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS FOR
 THE STRUCTURAL ROOF FRAMING AT THE SKYLIGHT OPENING.
 SHOW ALL CONNECTORS AND HANGERS. SPECIFY THE SIZE AND
 LOCATION OF THE SKYLIGHT OPENING ON THE PLANS. FBC
 107.2.1 & 301.1
  