| 2015-06-30 17:16:26 | 6/30/2015 |
| | PROJECT: COASTAL TOWERS. |
| | PERMIT#:15031064 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PAGES A-2.0, A-2.1, A-2.2, A-2.3, A,2.4, A-2.5, |
| | A-3.0, A-3.1, A-3.2A,3.3, |
| | THE ELECTRICAL RISER DIAGRAM NEEDS TO BE CORRECTED TO |
| | INDICATE THE CORRECT CONDUIT, WIRE SIZES AND TYPES. THE |
| | PLAN CURRENTLY INDICATES 2, 1/0 AND 1, #6 GROUND WIRES |
| | IN A 1" CONDUIT. THE PLAN DOES NOT INDICATE THE SYSTEM |
| | VOLTAGE BUT ASSUMING THE STANDARD 1PHASE VOLTAGE IS |
| | 120/240VOLT THIS CAN NOT BE ACHIEVED WITH THIS |
| | COBNFIGURATION UNLESS THE # 6 WIRE IS ACTUALLY AN |
| | UNDERSIZED NEUTRAL WIRE AND THE CONDUIT SYSTEM IS THE |
| | ACTING EQUIPMENT GROUND. PLEASE REVISE THE PLAN TO |
| | INDICATE THE TYPE OF WIRE ALUMINUM OR COPPER AND USING |
| | THE TABLES IN THE BACK OF THE NEC INDICATE THE CORRECT |
| | CONDUIT AND WIRE COMBINATION. THE WIRE AND CONDUIT |
| | COMBINATION CURRENTLY INDICATED ON THE PLAN WILL NOT |
| | WORK. THE WIRE SHOWN WILL NOT FIT IN A 1" CONDUIT. ALSO |
| | CORRECT THE WRITTEN DESCRIPTION TO INCLUDE THE SYTEM |
| | VOLTAGE AND THE CORRECT TERMINOLOGY FOR EACH OF THE |
| | CONDUCTORS. |
| | |
| | 1A) NOTE 7 INDICATES THE USE OF THINWALL CONDUIT OR |
| | ROMEX. ROMEX IS NOT APPROVED FOR USE IN A HIGH RISE. |
| | |
| | 1B) THE PLAN ELECTRICAL NOTES 22 AND 23 INDICATE THE |
| | INSTALLATION OF SMOKE AND CARBON MONOXIDE DETECTORS IN |
| | COMPLIANCE WITH FBC-R 314, 315, THEN THE NEW FIRE ALARM |
| | SYSTEM PLANS SUBMITTED INDICATE THE REPLACEMENT OF AN |
| | EXISTING FIRE ALARM SYSTEM. WILL BOTH TYPES OF SYSTEMS |
| | BE INSTALLED? PLEASE CLARIFY. |
| | |
| | 2) INDICATE THE EXISTANCE OR INSTALLATION OF REQUIRED |
| | EGRESS LIGHTING THROUGHOUT IN COMPLIANCE WITH NEC |
| | 700.12 AND 700.16 |
| | |
| | 3) A SEPARATE PERMIT APPLICATION ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | IS REQUIRED FOR THE FIRE ALARM SYSTEM. THE FIRE ALARM |
| | SYSTEM IS NOT A PART OF THIS PLAN REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |