| 2015-04-18 08:49:04 | 1) SHT.A-1 - GENERAL NOTES #1 - STATES THE CONSTRUCTION |
| | IS TO COMPLY WITH THE 2010 FBC- RESIDENTIAL. THIS |
| | BUILDING IS OUTSIDE THE PARAMETERS AND SHALL COMPLY |
| | WITH THE 2010 FBC- BUILDING. REVISE THE NOTE. |
| | 2) SHT. A-7.1 - THE CLEAR INSIDE DIMENSIONS FOR THE |
| | HANDICAP SHOWER SHALL BE 36 INCHES BY 36 INCHES CLEAR. |
| | FAC SEC.608.2.1. |
| | 3) THE WIDTH OF THE ACCESSIBLE BATHROOM SHALL BE A |
| | MINIMUM OF 85 INCHES. TO ALLOW FOR THE REQUIRED SPACING |
| | OF THE FIXTURES. 86 INCHES IN WIDTH ALLOWS FOR |
| | CONSTRUCTION TOLERANCES. |
| | 4) SHT. A-7.2 - THE HEIGHT OF THE GRAB BARS SHALL BE |
| | MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE |
| | GRIPPING SURFACE PER SEC.609.4 OF THE 2010 FAC. |
| | 5) SHT. A-7.2 - HANDICAP STALL DETAIL - REMOVE |
| | REFERENCE TO THE 2007 FBC. |
| | 6) SHOW THE WIDTH OF THE STANDARD SHOWERS ON THE PLAN. |
| | SHOWERS SHALL BE A MIN. OF 30 INCHES WIDE AND A MIN. OF |
| | 900 SQUARE INCHES PER THE FPC SEC.417.4. |
| | 7) SUBMIT A SANITARY AND WATER RISER FOR THE CHANGES TO |
| | THE PLUMBING SYSTEM IN HANDICAP ACCESSIBLE UNITS. WPB |
| | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| | 8) PROVIDE AN ELARGED FLOOR PLAN OF THE BATHROOMS AND |
| | KITCHENS SHOWING THE REQUIRED CLEAR FLOOR SPACE AT |
| | APPLIANCES AND BATHROOM FIXTURES. SHOW THE DIMENSIONS |
| | (L X W ) OF THE CLEAR FLOOR SPACES, NOT JUST BROKEN |
| | LINES. SHOW THE ROOM DIMENSIONS.COMPLY W/ 2010 FL. |
| | ACCESSIBILITY CODE CHAPT.6 & SEC. 804.WPB AMEND. TO |
| | 2010 FBC SEC. 107.2.1. |
| | 9) INDICATE ON THE PLANS THE TOTAL NUMBER OF UNITS IN |
| | THE STRUCTURE AND THE TOTAL NUMBER TO BE REMODELED. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |