| 2015-03-31 16:50:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | PER COMMENT # 23 ON EACH A-SHEET, A SMOKE ALARM SHALL |
| | BE INSTALLED IN EVERY GUEST ROOM AND EVERY LIVING AREA |
| | AND SLEEPING ROOM WITHIN A GUEST SUITE. THERE APPEARS |
| | TO BE MULTIPLE ROOMS, LIVING AREAS AND OUTSIDE SLEEPING |
| | ROOMS WHERE SMOKE DETECTORS ARE NOT INDICATED. PLEASE |
| | CORRECT. |
| | |
| | BASED ON THE LETTER OF INTENT AND PREVIOUS DISCUSSIONS |
| | REGARDING THE PHASING OF THE FIRE SPRINKLER SYSTEM AND |
| | HAVING EARLY DETECTION, A HEAT DETECTOR SHALL BE PLACED |
| | IN EACH KITCHEN AREA THAT IS ADDRESSIBLE AND CONNECTED |
| | TO THE FIRE ALARM SYSTEM. PLEASE ADD NOTE AND/OR |
| | INDICATE ON PLAN. |
| | |
| | PROVIDE THE RATING OF EACH DOOR LEADING TO THE EXIT |
| | CORRIDOR. THEY SHALL HAVE NOT LESS THAN A 20-MINUTE |
| | FIRE RATING. EACH DOOR SHALL BE SELF-CLOSING AND |
| | SELF-LATCHING. |
| | |
| | THE LETTER OF INTENT IN CONCEPT IS TENTATIVELY |
| | APPROVED. THE LETTER AND CONTENTS WILL BE ADDRESSED |
| | MORE SPECIFICALLY IN A SEPARATE RESPONSE LETTER FROM |
| | THE FIRE MARSHAL RELATED TO FIRE AND LIFE SAFETY |
| | CONCERNS. THE BUILDING DEPARTMENT MAY ADDRESS THEIR |
| | CONCERNS SEPARATELY. |
| | |
| | |
| | |
| | |