Plan Review Notes
Plan Review Notes For Permit 15031064
Permit Number 15031064
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-15 11:44:585/15/2015
 PROJECT: COASTAL TOWERS
 PERMIT#: 15031064
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE PLAN INCLUDES NOTES TO PROVIDE SMOKE DETECTORS
 AS REQUIRED BUT NONE ARE INDICATED ON THE FLOOR PLAN.
 PROVIDE THE RQUIRED SMOKE DETECTORS ON THE FLOOR PLAN
 AS REQUIRED BY THE FBC-R314, 315. WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 2) PROVIDE AND INDICATE THE REQUIRED DISCONNECT FOR THE
 A/C MECHANICAL EQUIPMENT. DISCONNECTING MEANS SHALL BE
 LOCATED WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM
 THE AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE
 DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED
 ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING
 EQUIPMENT. NEC 440.14
  
 3) PROVIDE AND INDICATE THE REQUIRED DISCONNECT FOR THE
 WATER HEATER. NEC 422.31
  
 4) INDICATE THE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE PANEL SCHEDULE.
  
 5) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC 2704
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  