| 2015-04-23 09:46:09 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031064 |
| | ADD: 1001 S. FLAGLER DR. / CHANGE OF OCCUPANCY/ |
| | DORMATORY |
| | CONT: GREENVIEW CONSTRUCTION |
| | TEL: (561)727-5013 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY/ APRIL 23RD/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THIS IS A |
| | RENOVATION OF 10 UNITS. FROM THE BEGINNING OF ALL THE |
| | MEETINGS BOTH THE FIRE DEPARTMENT AND BUILDING |
| | DEPARTMENT HAVE STATED THIS BUILDING WILL BE UNDER |
| | GOING A CHANGE IN OCCUPANCY FROM AN APARTMENT BUILDING |
| | TO A DORMATORY. PLEASE SEE THE 2010 FLORIDA EXISTING |
| | BUILDING CODE. 901.1 SCOPE. THE PROVISIONS OF THIS |
| | CHAPTER SHALL APPLY WHERE A CHANGE OF OCCUPANCY OCCURS, |
| | AS DEFINED IN SECTION 202, INCLUDING: (2.) WHERE THERE |
| | IS A CHANGE IN OCCUPANCY CLASSIFICATION OR THE |
| | OCCUPANCY GROUP DESIGNATION CHANGES. |
| | |
| | IN THIS CASE THE ORIGINAL USE AN APARTMENT BUILDING( |
| | CONDO) TO THE NEW USE OF A DORMATORY. BOTH USES ARE A |
| | R2 OCCUPANCY BUT THE OCCUPANCY GROUP DESIGNATION |
| | CHANGES, THE NAME THAT IDENTIFIES SOMEONE OR SOMETHING |
| | OR THE ACT OF INDICATING OR IDENTIFYING SOMEONE OR |
| | SOMETHING. |
| | |
| | DORMITORY. A SPACE IN A BUILDING WHERE GROUP SLEEPING |
| | ACCOMMODATIONS ARE PROVIDED IN ONE ROOM, OR IN A SERIES |
| | OF CLOSELY ASSOCIATED ROOMS, FOR PERSONS NOT MEMBERS OF |
| | THE SAME FAMILY GROUP, UNDER JOINT OCCUPANCY AND SINGLE |
| | MANAGEMENT, AS IN COLLEGE DORMITORIES OR FRATERNITY |
| | HOUSES. |
| | |
| | THIS REVIEW WILL CONTINUE UNDER THE CHANGE OF |
| | OCCUPANCY, THERE ARE CODE ISSUES ON THE PLANS THAT WERE |
| | NOT EVER DISCUSSED IN THE SERIES OF MEETINGS HELD SINCE |
| | DECEMBER OF 2014. |
| | 2010 FL EXST. BLDG. CODE 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A |
| | BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902 |
| | THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF |
| | OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A |
| | CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A |
| | DIFFERENT GROUP. |
| | |
| | 2A) THE PERMIT APPLICATION INDICATES IT IS FOR THE 1ST |
| | 10 UNITS THAT ARE UNDERGOING THE CHANGE IN USE, BUT THE |
| | COVER SHEET LIST UNDER SCOPE OF WORK PHASED WORK , |
| | UNITS COVERED UNDER THIS PHASE AND THE UNITS TO BE |
| | COVERED UNDER THE NEXT PHASE, ARE THERE ADDITIONAL |
| | PLANS GOING TO BE SUBMITTED FOR THE 2ND PHASE OR ARE WE |
| | TO COMMENT AS WELL ON THE NEXT PHASE SO THE SAME SET OF |
| | PLANS WOULD BE CONSIDERED MORE OF A MASTER AND THE |
| | CONTRACTOR WOULD ONLY NEED TO APPLY FOR A PERMIT |
| | APPLICATION SINCE THE REVIEWS WOULD HAVE BEEN UNDER THE |
| | 1ST PHASED PERMIT? ADDITIONAL INFORMATION IS REQUIRED, |
| | 107.2.1.3. |
| | |
| | 2B) SINCE THE PLANS INDICATE AND SHOW PHASED WORK ON |
| | THE PLANS PLEASE ALSO CONSIDER IF THE NEXT PHASE OF |
| | WORK HAS NOT APPLIED FOR PERMIT BEFORE JUNE 30/ 2015 |
| | NEW PLANS WILL BE REQUIRED, SINCE THE 5TH EDITION OF |
| | THE FLORIDA BUILDING CODE WILL BE ADOPTED STATEWIDE ON |
| | JULY 01/ 2015. |
| | |
| | 3A) THE DESIGNER OF RECORD HAS NOT INDICATED WHICH |
| | COMPLIANCE METHOD THEY ARE CHOSING UNDER THE 2010 FL. |
| | EXISTING BUILDING CODE 101.5 COMPLIANCE METHODS. THE |
| | EXCEPTION SUBJECT TO THE APPROVAL OF THE CODE OFFICIAL, |
| | ALTERATIONS COMPLYING WITH THE LAWS IN EXISTENCE AT THE |
| | TIME THE BUILDING OR THE AFFECTED PORTION OF THE |
| | BUILDING WAS BUILT. BOTH THE BUILDING CODE OFFICIAL AND |
| | FIRE OFFICIAL UNDER THE FIRE PREVENTION CODE HAVE MADE |
| | CERTIAN REQUIREMENTS TO TAKE PLACE BEFORE THE OCCUPANCY |
| | OF UNITS BEFORE THEY PHASED APPROVAL CAN TAKE PLACE, |
| | |
| | PLEASE SEE THE FIRE DEPARTMENTS (PETER LEDUC) COMMENTS |
| | ON WHAT WILL BE REQUIRED ON EACH PHASE. ONE EXCEPTION |
| | WE UNDERSTAND WILL BE THE SCISSOR STAIRS WILL BE |
| | ALLOWED TO REMAIN AS IS BECAUSE OF THE TECHNICAL |
| | RESTRAINTS. |
| | |
| | 3B) THE CODE ANALYSIS DOES NOT STATE THE NUMBER OF |
| | FLOORS NOR DOES THE CODE ANALYSIS STATE THE HEIGHT OF |
| | THE UPPER MOST OCCUPIABLE FLOOR, THE ROOF TOP DECK, |
| | FOUND ON SHEET A-6 THE PLANS STATE NO WORK ON THIS |
| | DECK. IS THIS BUILDING CONSIDERED A HIGH-RISE? |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. T |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | |
| | 4) ON ALL FLOORS THERE IS A TRASH CHUTE WITHOUT A |
| | ACCESS ROOM. |
| | THE EXST. BLDG. CODE 912.1.1.2 CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITH SEPARATION. WHERE A PORTION OF AN |
| | EXISTING BUILDING THAT IS CHANGED TO A NEW OCCUPANCY |
| | CLASSIFICATION AND THAT PORTION IS SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING WITH FIRE BARRIERS HAVING A |
| | FIRE-RESISTANCE RATING AS REQUIRED IN THE FLORIDA |
| | BUILDING CODE, BUILDING FOR THE SEPARATE OCCUPANCY, |
| | THAT PORTION SHALL COMPLY WITH ALL THE REQUIREMENTS OF |
| | CHAPTER 8 FOR THE NEW OCCUPANCY CLASSIFICATION AND WITH |
| | THE REQUIREMENTS OF THIS CHAPTER. |
| | 801.2 COMPLIANCE. IN ADDITION TO THE PROVISIONS OF THIS |
| | CHAPTER, WORK SHALL COMPLY WITH ALL OF THE REQUIREMENTS |
| | OF CHAPTERS 6 AND 7. THE REQUIREMENTS OF SECTIONS 703, |
| | 704, AND 705 SHALL APPLY WITHIN ALL WORK AREAS WHETHER |
| | OR NOT THEY INCLUDE EXITS AND CORRIDORS SHARED BY MORE |
| | THAN ONE TENANT AND REGARDLESS OF THE OCCUPANT LOAD. |
| | 703.2.1 EXISTING VERTICAL OPENINGS. ALL EXISTING |
| | INTERIOR VERTICAL OPENINGS CONNECTING TWO OR MORE |
| | FLOORS SHALL COMPLY WITH THE APPROPRIATE SECTIONS OF |
| | THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 5) SHEET A3 UNIT 401 THE ACCESSIBLE BATHROOM & KITCHEN |
| | AND ON SHEET A2 PHASE 2 UNIT 202 THE 2ND PHASE |
| | ACCESSIBLE UNIT WITH RESTROOM AND KITCHEN. |
| | 5A) BOTH UNITS WILL NEED TO COMPLY WITH AN ACCESSIBLE |
| | ENTRANCE WITH EITHER 18" ON THE LATCH SIDE OF THE ENTRY |
| | DOOR OR SUPPLY A ELECTRONIC PUSH PAD AND DOOR OPENER |
| | UNDER 103 EQUIVALENT FACILITATION. |
| | |
| | 5B) PROVIDE A ENLARGED DETAIL OF BATHROOMS AND KITCHENS |
| | AND THE REQUIRED CLEAR FLOOR SPACE FOR KITCHEN |
| | APPLIANCES AND BATHROOM FIXTURES, SUPPLY DIMENSIONS FOR |
| | THE ROOM SIZES. KITCHENS ARE TO COMPLY WITH THE |
| | ACCESSIBLITY CODE CHAPTER 804 AND CHAPTER 6 FOR THE |
| | BATHROOMS. |
| | |
| | 6) PLEASE PROVIDE HOW MANY SLEEPING ROOMS THERE ARE IN |
| | THE BUILDING. 2010 FL ACCESS. CODE 224.7 HOUSING AT A |
| | PLACE OF EDUCATION. |
| | HOUSING AT A PLACE OF EDUCATION SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR TRANSIENT LODGING GUEST ROOMS IN |
| | SECTIONS 224 AND 806, SUBJECT TO THE FOLLOWING |
| | EXCEPTIONS. THE TERM ?SLEEPING ROOM? IS INTENDED TO BE |
| | USED INTERCHANGEABLY WITH THE TERM ?GUEST ROOM? AS IT |
| | IS USED IN THE TRANSIENT LODGING STANDARDS. |
| | EXCEPTIONS: |
| | 1. KITCHENS WITHIN HOUSING UNITS CONTAINING ACCESSIBLE |
| | SLEEPING ROOMS WITH MOBILITY FEATURES (INCLUDING SUITES |
| | AND CLUSTERED SLEEPING ROOMS) OR ON FLOORS CONTAINING |
| | ACCESSIBLE SLEEPING ROOMS WITH MOBILITY FEATURES SHALL |
| | PROVIDE TURNING SPACES THAT COMPLY WITH SECTION 809.2.2 |
| | AND KITCHEN WORK SURFACES THAT COMPLY WITH SECTION |
| | 804.3. |
| | 2. MULTI-BEDROOM HOUSING UNITS CONTAINING ACCESSIBLE |
| | SLEEPING ROOMS WITH MOBILITY FEATURES SHALL HAVE AN |
| | ACCESSIBLE ROUTE THROUGHOUT THE UNIT IN ACCORDANCE WITH |
| | SECTION 809.2 |
| | |
| | 7) 224.1.2 GUEST ROOM DOORS AND DOORWAYS. |
| | ENTRANCES, DOORS, AND DOORWAYS PROVIDING USER PASSAGE |
| | INTO AND WITHIN GUEST ROOMS THAT ARE NOT REQUIRED TO |
| | PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | COMPLY WITH 404.2.3. |
| | EXCEPTION: SHOWER AND SAUNA DOORS IN GUEST ROOMS THAT |
| | ARE NOT REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING |
| | WITH 806.2 SHALL NOT BE REQUIRED TO COMPLY WITH |
| | 404.2.3. |
| | ADVISORY 224.1.2 GUEST ROOM DOORS AND DOORWAYS. |
| | BECAUSE OF THE SOCIAL INTERACTION THAT OFTEN OCCURS IN |
| | LODGING FACILITIES, AN ACCESSIBLE CLEAR OPENING WIDTH |
| | IS REQUIRED FOR DOORS AND DOORWAYS TO AND WITHIN ALL |
| | GUEST ROOMS, INCLUDING THOSE NOT REQUIRED TO BE |
| | ACCESSIBLE. THIS APPLIES TO ALL DOORS, INCLUDING |
| | BATHROOM DOORS, THAT ALLOW FULL USER PASSAGE. OTHER |
| | REQUIREMENTS FOR DOORS AND DOORWAYS IN SECTION 404 DO |
| | NOT APPLY TO GUEST ROOMS NOT REQUIRED TO PROVIDE |
| | MOBILITY FEATURES. |
| | |
| | 8) 224.2 GUEST ROOMS WITH MOBILITY FEATURES. IN |
| | TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH MOBILITY |
| | FEATURES COMPLYING WITH 806.2 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH TABLE 224.2. |
| | |
| | 9) 224.4 GUEST ROOMS WITH COMMUNICATION FEATURES. IN |
| | TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH |
| | COMMUNICATION FEATURES COMPLYING WITH 806.3 SHALL BE |
| | PROVIDED IN ACCORDANCE WITH TABLE 224.4. |
| | |
| | 10) 224.5 DISPERSION. GUEST ROOMS REQUIRED TO PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 806.2 AND GUEST ROOMS |
| | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| | WITH 806.3 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES |
| | OF GUEST ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF |
| | GUEST ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES |
| | COMPARABLE TO THE CHOICES PROVIDED TO OTHER GUESTS. |
| | WHERE THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO |
| | COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW FOR COMPLETE |
| | DISPERSION, GUEST ROOMS SHALL BE DISPERSED IN THE |
| | FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF BEDS, |
| | AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED TO |
| | PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH |
| | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED |
| | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS |
| | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| | WITH 806.3. |
| | |
| | 11) THE A.7 AND A7.1 BOTH SHOW WIND DESIGN CRITERIA AS |
| | A "C" EXPOSURE, WHEN YOU SHOOT A VECTOR OUT TO NORTH |
| | OVER THE INTERCOASTAL TO THE NORTH BRIDE THE DISTANCE |
| | OF CLEAR WATER IS OVER 5,000 FT. THE SAME HOLDS TRUE TO |
| | THE SOUTH WHEN A VECTOR IS SHOUT OUT TO THE SOUTH END |
| | OF EVERGLADES ISLAND ACROSS FROM PHIPPS PARK IN PALM |
| | BEACH, THIS IS ALSO OVER 5,000 FT PUTTING THE EXPOSURE |
| | AS A EXPOSURE "D". 2010 FBC-B 1609.4.2 EXPOSURE D. |
| | EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE |
| | ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS |
| | IN THE UPWIND DIRECTION FOR A DISTANCE OF AT LEAST |
| | 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND |
| | INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET |
| | (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, |
| | WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS |
| | DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | 12) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |