2015-04-22 12:57:191) SHT. P2.2 - SHOWS A DRAIN LINE INSTALLED ABOVE THE
 CEILING. INDICATE THE TYPE OF PIPING TO BE USED.
 INDICATE ON THE PLAN IF THE AREA ABOVE THE CELING IS A
 PLENUM. IF IT IS, MATERIALS SHALL COMPLY WITH 2010 FMC
 SEC.602.2.1.
 2) SUBMITMANUFACTURER'S SPECIFICATIONS FOR THE GREASE
 TRAP. SUBMIT SIZING CALCULATIONS PER 2010 FPC
 SEC.1003.2, 1003.3.4, 1003.4.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LITTLE
 GIANT DRAINASAUR PUMP. WPB AMND. TO 2010 FPC SEC.
 107.2.1.
 4) THE EJECTOR SHALL CONNECT TO THE THE DRAINAGE SYSTEM
 IN ACCORDANCE WITH 2010 FPC SEC.712.3.5.
 5) SHT. P2.2 - SHOWS A KEYNOTE SYMBOL #6 AT A FLOOR
 SINK NEXT TO THE GREASE TRAP YET THERE IS NO KEYNOTE #6
 IN THE PLANS. CLARIFY.
 6) THE WATER SUPPLY TO THE COFFEE MACHINE SHALL BE
 PROTECTED AGAINST BACKFLOW PER 2010 FPC SEC.608.16.10.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE WATER
 SOFTENER AND WATER FILTRATION SYSTEM. SUBMIT PIPING
 DETAILS.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 8) THE SINKS IN ROOMS # 1445 & # 1422 SHALL COMPLY WITH
 THE 2010 FAC SECS. 212 & 606. THE MAXIMUM HEIGHT OF THE
 COUNTER SHALL BE 34 INCHES AND A CLEAR FLOOR SPACE
 SHALL BE PROVIDED PER THE FAC SEC.606.2.
 9) IDENTIFY THE ROOM WITH THE SINK THAT IS ADJACENT TO
 ROOM # 1418. THE SINK IN THIS ROOM MAY HAVE TO COMPLY
 WITH THE FAC SECS.212 & 606.
 10) SHT. P5.1 - THE FOLLOWING PLUMBING VIOLATIONS
 EXIST:
 1) THE LAVATORIES IN THE MEN'S AND WOMEN'S RESTROOM DO
 NOT APPEAR TO BE VENTED AND APPEAR TO BE DRAWN AS "S"
 TRAPS. 2010 FPC SEC.901.1.1, 1002.3. CLARIFY.
 2) URINALS APPEAR TO BE "S" TRAPPED AS DRAWN. CLARIFY.
 3) THE DESIGN OF THE PLUMBING SYSTEM FOR THE MEN'S AND
 WOMEN'S RESTROOM DOES NOT COMPLY WITH THE PLUMBING CODE
 FOR A WET VENT SYSTEM OR A CIRCUIT SYSTEM (FPC 909 &
 911).
 4) SK-3 IN EXECUTIVE PREP AREA IS S-TRAPPED ON THE
 RISER. 2010 FPC SEC.901.1.1, 1002.3. CLARIFY.
 5) SIZE ALL SECTIONS OF THE VENTING SYSTEM FOR THE NEW
 PLUMBING FIXTURES ( LAVS, JANITOR SINK, ETC.)
 6) THE WASHING MACHINE SALL DISCHARGE INTO A 3" STACK
 PER THE 2010 FPC SEC.406.3.
 7) THE FLOOR DRAIN COLLECTING THE PAN DRAINS IS NOT
 CONNECTED TO ANYTHING ON THE RISER. CLARIFY.
 11) IF THERE ARE GAS APPLIANCES IN THE EXECUTIVE PREP
 AREA, SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT AND SUBMIT A GAS RISER FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
  
  