| 2015-04-25 13:18:27 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15031026 |
| | W. P. B. PERMIT: 14060196 |
| | ADD: 777 S. FLAGLER DR. 12TH/ 14 TH FLOORS |
| | CONT: WOOLEMS |
| | TEL: ( |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. APRIL 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) PAGE 014- A1.09 IN COMPARE MODE THERE ARE MANY |
| | REVISIONS MADE TO THE PLANS THE ARE NOT CLOUDED. NEW |
| | EXTERIOR DOORS IN THE EXECUTIVE OFFICE 420, NO DETAILS |
| | THROUGH PROVIDEING FRAMING, SILL ETC. |
| | |
| | 2) PAGE 014- A1.09 IN COMPARE MODE, VERSION # 2 NEW |
| | DOORS 1405I & 1405J SHOW BUT THERE IS NO INFORMATION |
| | WHAT THESE ROOMS ARE TO BE USED FOR, THEY ARE GRAY |
| | BOXED WHICH IS ASSUMED COMMON AREAS SUCH FOR TELEPHONE, |
| | ELECTRICAL ROOMS AND OR EQUIPMENT ROOMS? 107.2.1 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) PAGE 014-A1.09 IN COMPARE MODE, VERSION #2 NOT |
| | HIGHLIGHTED BATHROOMS 1432 & 1433 IN VERSION 1 WHEREAS |
| | IN VERSION # 2 ROOM 1432 IS NOW A JANITORS CLOSET AND |
| | ROOM 1433 IS NOW A RESTROOM. DETAIL 10/ A7.11 IN |
| | VERSION 2 NO SUCH SHEET IN THIS REVISION. CN NOT |
| | DETERMINE CODE COMPLIANCE. |
| | |
| | 4) PAGE 014-A1.09 IN COMPARE MODE CORRIDOR 1434 DOOR # |
| | 1434C WAS REMOVED FROM THE EXISITNG ELEVATOR LOBBY, |
| | THIS WILL AFFECT THE PRESSURIZATION OF THE ELEVATOR |
| | HOISTWAY, MAY NEED TO BE TESTED TO SEE IF THE INCREASED |
| | ROOM AREA EFFECTS THE REQUIRED PRESSURIZATION OF THE |
| | SHAFTWAY. 909.6.1 MINIMUM PRESSURE DIFFERENCE. |
| | |
| | 5) PAGE 014-A1.09 IN COMPARE MODE NATES OFFICE EXTERIOR |
| | DOOR CHANGED FROM DOUBLE DOORS TO SINGLE DOOR. NOT |
| | BUBBLED AS A REVISION, THE SAME WITH EXTERIOR DOOR |
| | 1447, PLEASE PROVIDE BUBBLES AND REVISION MARKERS. DOOR |
| | 1451A IS RELOCATED NOT HIGHLIGHTED AS A REVISON. DOOR |
| | 1412A HAS BEEN RELOCATED NO BUBBLE OR REVION MARKER. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. PLEASE SEE FIRE COMMENTS ABOUT UPDATE OF |
| | REVISIONS NOT APPEARING AS HIGHLIHTED OR MARKED AS A |
| | REVISION. UPDATE PLANS AND ALSO SUBMIT A WRITTEN |
| | NARRATIVE OF ALL THE CHANGES. |
| | |
| | 6) PAGE 023 A1.21 IN COMPARE MODE THE ROOMS AND DOORS |
| | ARE NOT LABELED THERE IS NO WAY TO IDENTIFY CHANGES |
| | BETWEEN VERSION 1 & VERSION 2 OTHER THAN TO CLOULD WHAT |
| | MAYBE ISSUES, AGAIN THERE IS NO BUBBLES OR REVISION |
| | MARKERS WHEN IN COMPARE MODE. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. PLEASE SEE FIRE |
| | COMMENTS ABOUT UPDATE OF REVISIONS NOT APPEARING AS |
| | HIGHLIHTED OR MARKED AS A REVISION. |
| | |
| | THIS REVIEW WILL END, NO WAY OF IDENTIFYING ITEMS |
| | WITHOUT ROOM AND DOOR IDENTIFICATION!!!!! A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |