Plan Review Notes
Plan Review Notes For Permit 15031026
Permit Number 15031026
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-25 13:18:27BUILDING PLAN REVIEW
 W. P. B. REVISION: 15031026
 W. P. B. PERMIT: 14060196
 ADD: 777 S. FLAGLER DR. 12TH/ 14 TH FLOORS
 CONT: WOOLEMS
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. APRIL 25/ 2015
 ACTION: DENIED
  
 1) PAGE 014- A1.09 IN COMPARE MODE THERE ARE MANY
 REVISIONS MADE TO THE PLANS THE ARE NOT CLOUDED. NEW
 EXTERIOR DOORS IN THE EXECUTIVE OFFICE 420, NO DETAILS
 THROUGH PROVIDEING FRAMING, SILL ETC.
  
 2) PAGE 014- A1.09 IN COMPARE MODE, VERSION # 2 NEW
 DOORS 1405I & 1405J SHOW BUT THERE IS NO INFORMATION
 WHAT THESE ROOMS ARE TO BE USED FOR, THEY ARE GRAY
 BOXED WHICH IS ASSUMED COMMON AREAS SUCH FOR TELEPHONE,
 ELECTRICAL ROOMS AND OR EQUIPMENT ROOMS? 107.2.1
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) PAGE 014-A1.09 IN COMPARE MODE, VERSION #2 NOT
 HIGHLIGHTED BATHROOMS 1432 & 1433 IN VERSION 1 WHEREAS
 IN VERSION # 2 ROOM 1432 IS NOW A JANITORS CLOSET AND
 ROOM 1433 IS NOW A RESTROOM. DETAIL 10/ A7.11 IN
 VERSION 2 NO SUCH SHEET IN THIS REVISION. CN NOT
 DETERMINE CODE COMPLIANCE.
  
 4) PAGE 014-A1.09 IN COMPARE MODE CORRIDOR 1434 DOOR #
 1434C WAS REMOVED FROM THE EXISITNG ELEVATOR LOBBY,
 THIS WILL AFFECT THE PRESSURIZATION OF THE ELEVATOR
 HOISTWAY, MAY NEED TO BE TESTED TO SEE IF THE INCREASED
 ROOM AREA EFFECTS THE REQUIRED PRESSURIZATION OF THE
 SHAFTWAY. 909.6.1 MINIMUM PRESSURE DIFFERENCE.
  
 5) PAGE 014-A1.09 IN COMPARE MODE NATES OFFICE EXTERIOR
 DOOR CHANGED FROM DOUBLE DOORS TO SINGLE DOOR. NOT
 BUBBLED AS A REVISION, THE SAME WITH EXTERIOR DOOR
 1447, PLEASE PROVIDE BUBBLES AND REVISION MARKERS. DOOR
 1451A IS RELOCATED NOT HIGHLIGHTED AS A REVISON. DOOR
 1412A HAS BEEN RELOCATED NO BUBBLE OR REVION MARKER.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE SEE FIRE COMMENTS ABOUT UPDATE OF
 REVISIONS NOT APPEARING AS HIGHLIHTED OR MARKED AS A
 REVISION. UPDATE PLANS AND ALSO SUBMIT A WRITTEN
 NARRATIVE OF ALL THE CHANGES.
  
 6) PAGE 023 A1.21 IN COMPARE MODE THE ROOMS AND DOORS
 ARE NOT LABELED THERE IS NO WAY TO IDENTIFY CHANGES
 BETWEEN VERSION 1 & VERSION 2 OTHER THAN TO CLOULD WHAT
 MAYBE ISSUES, AGAIN THERE IS NO BUBBLES OR REVISION
 MARKERS WHEN IN COMPARE MODE. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. PLEASE SEE FIRE
 COMMENTS ABOUT UPDATE OF REVISIONS NOT APPEARING AS
 HIGHLIHTED OR MARKED AS A REVISION.
  
 THIS REVIEW WILL END, NO WAY OF IDENTIFYING ITEMS
 WITHOUT ROOM AND DOOR IDENTIFICATION!!!!! A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  