| Plan Review Notes For Permit 15030974 |
| Permit Number |
15030974 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-28 09:53:30 | 1) VERIFY ALL NEW GENERAL PURPOSE OUTLETS MUST BE | | | TAMPER RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | | | 2) PROVIDE A PANELSCHEDULE FOR THE INSPECTOR IN THE | | | FIELD PRIOR TO FINAL. EVERY CIRCUIT AND CIRCUIT | | | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS | | | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|