Plan Review Notes
Plan Review Notes For Permit 15030965
Permit Number 15030965
Review Stop E
Sequence Number 2
Notes
Date Text
2015-07-13 14:33:177/13/2015
 PROJECT: GRASSY WATERS NATURE CENTER
 PERMIT#:15030965
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 PG. E4.1
 1) THE EXISTING ESTIMATED DEMAND LOAD INDICATED ON
 BANCH PANEL "A" DOES NOT INCLUDE ALL LOADS. A NOTE AT
 THE TOP OF THE PANEL SCHEDULE INDICATES THAT SEVERAL
 CIRCUITS WILL BE DISCONNECTED VIA CONTACTOR DURING A
 30DAY PERIOD FOR LOAD READING ALLOWED PER NEC 220.87(1)
 EX.
 THE TOTAL ESTIMATED DEMAND CURRENTLY INDICATED ON
 BRANCH PANEL "A" IS ALREADY ALMOST 100% OF THE CAPACITY
 OF THE EXISTING 150A MAIN OCPD.
  
 2) WHAT IS THE TOTAL OF THE LOADS TO BE DISCONNECTED?
  
 3) CLARIFY THE INTENT OF THE DESIGNER IF THE TOTAL
 CONNECTED DEMAND LOAD DETERMINED FROM A 30DAY READING
 PLUS THE EXISTING DISCONNECTED LOADS EXCEEDS THE
 CAPACITY OF THE EXISTING MAIN OCPD.
  
 4) WHAT IS THE CAPACITY OF THE EXISTING METER
 ENCLOSURE?
  
 5) WHAT IS THE CAPACITY OF BRANCH PANEL "A" BUSS AND
 ENCLOSRE?
  
 6) WHAT IS THE SIZE OF THE EXISTING GROUNDING ELECTRODE
 CONDUCTOR?
  
 E3.1
 7) VERIFY OR INSTALL THE REQUIRED GFI RECEPTACLE WITHIN
 SIGHT OF THE MECHANICAL EQUIPMENT ON THE ROOF. NEC
 210.63 SEE 210.8(A)(3),
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  