| Date |
Text |
| 2015-07-13 14:33:17 | 7/13/2015 |
| | PROJECT: GRASSY WATERS NATURE CENTER |
| | PERMIT#:15030965 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | PG. E4.1 |
| | 1) THE EXISTING ESTIMATED DEMAND LOAD INDICATED ON |
| | BANCH PANEL "A" DOES NOT INCLUDE ALL LOADS. A NOTE AT |
| | THE TOP OF THE PANEL SCHEDULE INDICATES THAT SEVERAL |
| | CIRCUITS WILL BE DISCONNECTED VIA CONTACTOR DURING A |
| | 30DAY PERIOD FOR LOAD READING ALLOWED PER NEC 220.87(1) |
| | EX. |
| | THE TOTAL ESTIMATED DEMAND CURRENTLY INDICATED ON |
| | BRANCH PANEL "A" IS ALREADY ALMOST 100% OF THE CAPACITY |
| | OF THE EXISTING 150A MAIN OCPD. |
| | |
| | 2) WHAT IS THE TOTAL OF THE LOADS TO BE DISCONNECTED? |
| | |
| | 3) CLARIFY THE INTENT OF THE DESIGNER IF THE TOTAL |
| | CONNECTED DEMAND LOAD DETERMINED FROM A 30DAY READING |
| | PLUS THE EXISTING DISCONNECTED LOADS EXCEEDS THE |
| | CAPACITY OF THE EXISTING MAIN OCPD. |
| | |
| | 4) WHAT IS THE CAPACITY OF THE EXISTING METER |
| | ENCLOSURE? |
| | |
| | 5) WHAT IS THE CAPACITY OF BRANCH PANEL "A" BUSS AND |
| | ENCLOSRE? |
| | |
| | 6) WHAT IS THE SIZE OF THE EXISTING GROUNDING ELECTRODE |
| | CONDUCTOR? |
| | |
| | E3.1 |
| | 7) VERIFY OR INSTALL THE REQUIRED GFI RECEPTACLE WITHIN |
| | SIGHT OF THE MECHANICAL EQUIPMENT ON THE ROOF. NEC |
| | 210.63 SEE 210.8(A)(3), |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |