| 2015-04-11 11:28:36 | 4/11/2015 |
| | PROJECT: GRASSY WATERS NATUER CENTER RENNOVATION |
| | PERMIT#: 15030965 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) E0.2 |
| | REVISE THE CODE REFERANCES TO INDICATE THE USE OF THE |
| | 2010 EDITION OF THE FLORIDA BUILDING CODE. |
| | |
| | 2) E2.1 |
| | VERIFY AND INDICATE THE EXISTANCE OF THE REQUIRED |
| | EMERGENCY AND EXIT LIGHTING ON THE LIGHTING PLAN IN THE |
| | EXISTING EXHIBIT ROOM OR PROVIDE IT. NFPA 101 SECTION |
| | 7.10.1.5.1, AND NEC 700.16. |
| | VERIFY AND INDICATE RECESSED LUMINAIRES INSTALLED IN |
| | THE BUILDING THERMAL ENVELOPE ARE SEALED TO LIMIT AIR |
| | LEAKAGE BETWEEN CONDITIONED AND UNCONDITIONED SPACES. |
| | FBC-E 502.3.8 |
| | |
| | 3) E2.1 |
| | VERIFY OR INSTALL THE REQUIRED GFI RECEPTACLE WITHIN |
| | SIGHT OF THE MECHANICAL EQUIPMENT. NEC 210.63 SEE |
| | 210.8(A)(3), |
| | VERIFY OR INSTALL THE REQUIRED GFI RECEPTACLES FOR USE |
| | WITH THE EXISTING DRINKING FOUNTAINS. NEC 422.52 |
| | |
| | 4) E4.1 |
| | INDICATE THE LOCATION OF THE EXISTING ELECTRICAL |
| | UTILITY METER. WPB AMENDMENTS TO FBC 107.3.2 |
| | THE RISER INDICATES PANEL "A" BEING FED DIRECTLY FROM |
| | THE METER. VERIFY THE EXISTANCE OF THE FIRST MEANS OF |
| | DISCONNECT IN COMPLIANCE WITH THE NEC 230.70. |
| | VERIFY THE EXISTING LOAD ON THE EXISTING ELECTRICAL |
| | SERVICE TO DETERMINE THE AVAILABLE CAPACITY FOR THE |
| | ADDED LOAD OF THE NEW PANEL B AND ASSOCIATED LOADS. |
| | VERIFY AND INDICATE THE SIZE AND TYPE OF CONDUCTORS IN |
| | THE RACEWAY FEEDING EXISTING PANEL "A" NEC 215.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |