| 2015-05-14 15:01:10 | 5/14/2015 |
| | PROJECT: LAUNDRY |
| | PERMIT#: 15030959 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 4TH ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) IDENDIFY THE SCALE. WPB AMENDMENTS TO THE FBC |
| | 107.2.1 THROUGH 107.2.5 |
| | |
| | 2)THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. NEC 700.12(F) |
| | |
| | 3) VERIFY THE ALLOWABLE AMPACITY OF EACH CONDUCTOR |
| | SHALL BE REDUCED AS SHOWN IN TABLE 310.15(B)(2)(A). SEE |
| | ANNEX B |
| | |
| | 4) BOXES AND CONDUIT BODIES SHALL BE OF SUFFICIENT SIZE |
| | TO PROVIDE FREE SPACE FOR ALL ENCLOSED CONDUCTORS. IN |
| | NO CASE SHALL THE VOLUME OF THE BOX, AS CALCULATED IN |
| | 314.16(A), BE LESS THAN THE FILL CALCULATION AS |
| | CALCULATED IN 314.16(B). THE MINIMUM VOLUME FOR CONDUIT |
| | BODIES SHALL BE AS CALCULATED IN 314.16(C). NEC 314.16 |
| | |
| | 5) USE ANNEX C, THE CONDUIT AND TUBING FILL TABLES TO |
| | DETERMINE THE MAXIMUM FILL CAPACITY FOR CONDUCTORS AND |
| | FIXTURE WIRES OF THE SAME SIZE IN CONDUIT OR TUBING |
| | USED. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |