| 2015-05-12 16:04:15 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) "B PHASE 208V TO GROUND ON A 120/240 DELTA HI LEG |
| | ELECTRICAL DISTRIBUTION SYSTEM. THERE SHOULD BE NO |
| | SINGLE POLE 120V BREAKERS INSERTED INTO ANY "B" PHASE |
| | SLOTS IN ANY 3 PHASE DELTA PANEL BOARDS. |
| | |
| | 2) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS NOT READILY APPARENT TO THE |
| | OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 |
| | |
| | 3) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| | |
| | 4) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT |
| | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL |
| | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND |
| | BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC |
| | 700.12(F) |
| | |
| | 5) VERIFY CONDUIT AND BOX FILL AS WELL AS CONDUCTOR |
| | DERATING. |
| | |
| | 6) CORRECT THE SCALE THE PLAN IS DESIGNED TO. |
| | |
| | 7) CORRECT THE SIZE OF THE ARCHITACT'S SEAL. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |