| 2015-04-06 12:03:03 | 4/6/2015 |
| | PROJECT: LAUNDRY |
| | PERMIT#: 15030959 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WPB AMENDMENTS TO THE FBC 107.3.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. THE ELECTRICAL PLAN |
| | SUBMITTED ON SHEET E-1 INDICATES ALL ELECTRICAL |
| | CIRCUITRY IS EXISTING. HOWEVER, SHEET A-1 INDICATES THE |
| | INSTALLATION OF 3 NEW DRYERS AND 17 NEW WASHERS, |
| | A) PROVIDE A RISER DIAGRAM TO INDICATE THE ELECTRICAL |
| | SERVICE ENTRANCE, ALL MAIN OCPD(S) AND PANELS. |
| | B) PROVIDE PANEL SCHEDULES INCLUDING THE OCPD(S) AND |
| | WIRE SIZES FOR ALL AFFECTED CIRCUITRY AND FEEDERS. |
| | C) PROVIDE LOAD CALCULATIONS FOR THE PANELS AND FOR THE |
| | ELECTRICAL SERVICE. |
| | |
| | 2) WPB AMENDMENTS TO THE FBC 107.3.2 |
| | A) ADDITIONAL CLARIFICATION IS REQUIRED. INDICATE ALL |
| | CIRCUITRY ON THE FLOOR PLAN. INDICATE WHAT IS EXISTING |
| | TO REMAIN AND WHAT IS PROPOSED TO BE NEW. |
| | B) INDICATE THE REQUIRED MEANS OF DISCONNECT FOR ALL |
| | FIXED IN PLACE APPLIANCES. NEC 422 |
| | |
| | 3) NEC 700.12, 700.16 |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS EMERGENCY AND |
| | EXIT LIGHTING EQUIPMENT SHALL BE CLEARLY IDENTIFIED AT |
| | THE DISTRIBUTION PANEL. NEC 700.12 |
| | EMERGENCY LIGHTING SHALL BE DESIGNED AND INSTALLED SO |
| | THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, |
| | SUCH AS THE BURNING OUT OF A LAMP, CANNOT LEAVE IN |
| | TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY |
| | ILLUMINATION. INDICATE THE REQUIRED EMERGENCY AND EXIT |
| | LIGHTING ON THE LIGHTING PLAN. NEC 700.16 |
| | |
| | 4)NEC 422.60 |
| | PROVIDE EQUIPMENT MANUFACTURER DOCUMENTATION FOR ALL |
| | NEW EQUIPMENT INDICATING LISTING REQUIREMENTS AND |
| | ELECTRICAL CHARACTERISTICS SUCH AS LOAD, VOLTAGE AND |
| | FREQUENCY. NEC 422.60 |
| | |
| | 5) WPB AMENDMENTS TO THE FBC 107.3.2 |
| | IDENTIFY ROOM DESIGNATIONS ON THE FLOOR PLAN AND |
| | INDICATE THE LOCATIONS FOR THE ELECTRICAL SERVICE |
| | ENTRANCE METER/MAINS EQUIPMENT AND PANELS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |