Date Text
2015-06-22 10:44:14APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) REVISE THE TRUSS ANCHOR FOR MARK C ON SHEET S-2. THE
 ALLOWABLE UPLIFT LOAD FOR THE DOUBLE SIMPSON HETA
 ANCHOR IS 2500. THE ANCHOR SCHEDULE SPECIFIES THE
 ALLOWABLE UPLIFT FOR (2) HETA 16 ANCHORS AS 3620.
 2) SUBMIT TWO CURRENT SETS OF PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. THE ONE THAT WAS
 SUBMITTED, NOA NO. 06-0914.04, EXPIRED ON 11/16/2011.
 3) SPECIFY THE ROOFING ASSEMBLY AND MAXIMUM DESIGN
 PRESSURE FOR THE CERTAINTEED MODIFIED BITUMEN ROOF
 SYSTEM THAT WILL BE INSTALLED. THE FLAT ROOF CORNER
 AREAS REQUIRE A DESIGN PRESSURE OF -104.8 PSF PER THE
 WINDLOAD TABLE ON SHEET S-2.