| 2015-04-08 09:25:13 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030908 |
| | ADD: 6300 GARDEN AVE. |
| | CONT: GULF ATLANTIC ROOFING |
| | TEL: ( 561)714-5191 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 2ND REVIEW |
| | DATE: WED. APRIL 08/ 2015 |
| | ACTION: DENIED |
| | |
| | 1A) NOA JOHN MANVILLE INSULATION NOA 14-1015.08 THE |
| | CONTRACTOR HAS NOT CIRCLED (IDENTIFIED) WHICH |
| | INSULATION WILL BE APPLIED TO THE 2ND STORY ROOFING |
| | PERMIT. |
| | |
| | 1B) GAF RUBEROID MODIFIED BITUMEN ROOF SYSTEMS OVER |
| | WOOD DECK NOA 14-0611.01 THE CONTRACTOR OF RECORD HAS |
| | INDICATED ON THE FRONT SHEET OF THIS NOA SYSTEM SYSTEM |
| | TYPE A(1) PAGE 8. THIS SUB-SYSTEM STARTS ON PAGE 7 |
| | CONTINUES TO PAGE 8, PLEASE CIRCLE WHICH SUB-SYSTEM IS |
| | TO BE INSTALLED. NOTE LIMITATION # 7 WITH ENHANCED |
| | FASTENING REQUIREMENTS BY ENGINEER. |
| | |
| | 1C) THE ENGINEERING LETTER SUBMITTED IS GENERIC, NOT |
| | SITE SPECIFIC TO LOCATION OF WORK, DOES NOT REFERENCE |
| | THE PRODUCT APPROVAL NUMBER. NOR THE SUB-SYSTEM, THE |
| | MAXIMUM DESIGN PRESSURES FOR THE SUB-SYSTEM NOR THE |
| | LIMITATION 7 OR 9. THE ENGINEER FAILS TO PROVIDE THE |
| | FASTENER TYPE AS PER SUB-SYSTEM AND THE AMOUNT OF |
| | REQUIRED ROWS FOR THE WIDTH OF THE PRODUCT. DEPENDING |
| | ON THE SUB-SYSTEMS THEY PROVIDE THE AMOUNT OF ROWS OR |
| | THE SPACING BETWEEN ROWS. |
| | |
| | CALLED AND SPOKE WITH P. E. ALBERT KWAN |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR ROOF |
| | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |